34 GMC-I Messtechnik GmbH
9.4.1.
Configuration via the Ethernet Port
A crossover patch cable must be used for direct connection of the SMARTCONTROL to the PC (included with the
SMARTCONTROL).
Each SMARTCONTROL has the following static IP address as a default setting: 192.168.130.190. There are two
possibilities for data exchange:
Either IP address 192.168.130.XXX and subnet mask 255.255.255.0 are selected at the PC or notebook (XXX being
a number between 1 and 254 but not 190).
The TCP/IP address at the SMARTCONTROL is changed (possible without changing the PC’s IP).
The procedure is described in detail in the SMARTCONTROL Manager manual beginning with the section entitled
“Setting Up Projects, Buildings and SMARTCONTROLs”.
9.4.2.
Configuration via Analog Modem or ISDN
A PC with an analog modem or an ISDN adapter with corresponding telephone line must be used.
Please note: The ISDN module in the SMARTCONTROL cannot be queried by an analog modem without additional
hardware.
Start Gossen Metrawatt “SMARTCONTROL Manager” software, and then establish connection and configure the
SMARTCONTROL as described in the manual beginning with the section entitled “Setting Up Projects, Buildings
and SMARTCONTROL”].
9.4.3.
Deleting the Password
a)
Press and hold the F1 key [see item 14 in section 6. , “Connections Overview,”].
b)
Briefly press the reset key [see item 15 in section 6. , “Connections Overview,”].
c)
Release the F1 key.
d)
Wait until the DIAG LED goes out [see item 19 in section 6. , “Connections Overview,”].
e)
Press and hold the F1 key (max. 5 seconds) until the DIAG LED starts blinking.