Component Identi
fi
cation
CB10
Circuit Breakers Inside Alternator Assembly
Figure 20
Ref.
Size
Component
CB10
90 A
120/240V Alternator
Circuit Breaker Configuration Options
Improper configuration can result in electric shock.
All changes from the recommended circuit breaker
configuration must meet all National, State,
and Local safety and electrical codes. Consult
a qualified electrician before attempting any
changes. See page 27 and 28 for correct circuit
breaker configuration.
The Electrical Enclosure (DB) circuit breaker
configuration described in the tables on the previous
page is the recommended configuration.
Sub-Panel Options
Some customer changes are acceptable to
accommodate larger loads from auxiliary equipment
or a sub-panel. It is suggested that circuit breakers
CB04 be substituted to accommodate larger loads
or a sub-panel. The total auxiliary equipment
loads added to the configuration must be limited
to the system’s available auxiliary current. See
Proportioner Models, page 9, for available auxiliary
current at 240V, 60Hz.
See the Reactor repair manual for optional circuit
breakers and their current ratings. Circuit breakers
used must meet UL489 specifications.
Auxiliary Wiring Diagram Options.
The generator supplies power in a 3-wire,
single-phase, mid-point neutral wiring configuration.
For 240 VAC loads, wire the load across the output
terminals of the circuit breaker. For 120 VAC loads,
wire the load between the neutral terminal blocks
next to the three pole main power switch (CT01)
to one pole of the circuit breaker. See electrical
diagrams in Reactor repair manual.
Disable LPTCMs For Booster Heat
Both LPTCMs for booster heat must be disabled to
allow use of power for additional auxiliary power.
1.
Follow Shutdown instructions. See
2.
Refer to Disable Optional Booster Heater Wiring
Diagram in the Reactor repair manual.
To replace or repair a circuit breaker, use the
following steps:
1.
Follow Shutdown instructions. See
2.
Refer to circuit breaker identification table and
electrical diagrams in Reactor repair manual.
3.
Loosen four screws connecting wires and bus
bar to circuit breaker that will be replaced.
Disconnect wires.
4.
Pull locking tab out 1/4 in. (6mm) and pull circuit
breaker away from the din rail. Install new circuit
breaker. Insert wires and tighten down all screws.
3A1705E
29
Summary of Contents for 259079
Page 34: ...Setup A5 A1 A2 AS AN A3 AT A3 A4 A2 A6 A4 34 3A1705E...
Page 45: ...Advanced Display Module ADM Operation Setup Screens Navigation Diagram Figure 35 3A1705E 45...
Page 49: ...Advanced Display Module ADM Operation Run Screens Navigation Diagram Figure 36 3A1705E 49...
Page 93: ...Dimensions Dimensions Top View Figure 43 Side View Figure 44 3A1705E 93...
Page 95: ...Dimensions Pallet Mounting Dimensions Figure 48 3A1705E 95...
Page 97: ...Notes Notes 3A1705E 97...