Shutdown
Shutdown
NOTICE
Proper system setup, startup, and shutdown
procedures are critical to electrical equipment
reliability. The following procedures ensure steady
voltage. Failure to follow these procedures will
cause voltage fluctuations that can damage
electrical equipment and void the warranty.
1. Press
to stop the pumps.
2. Turn off heat zones.
3. Relieve pressure. See
Pressure Relief Procedure, page 64.
4. Press
to park the Component A Pump.
5. Press
to deactivate the system.
6. Turn off the air compressor, air dryer, and
breathing air.
7. Close the main air shutoff valve.
8. Turn main power switch OFF.
To prevent electric shock do not remove any
shrouds or open the electrical enclosure door.
240 V is still present in the system until the
engine has stopped.
9. Allow engine dwell time.
NOTICE
Allow engine dwell time, per manufacturer
recommendations, prior to shutdown. Dwell
time will help engine cool down after running at
operating temperature for any period of time.
10. Press
on the engine control module.
11. Open air compressor bleed valve to relieve
pressure and remove water from tank.
12. Close all fluid supply valves.
3A1705E
63
Summary of Contents for 259079
Page 34: ...Setup A5 A1 A2 AS AN A3 AT A3 A4 A2 A6 A4 34 3A1705E...
Page 45: ...Advanced Display Module ADM Operation Setup Screens Navigation Diagram Figure 35 3A1705E 45...
Page 49: ...Advanced Display Module ADM Operation Run Screens Navigation Diagram Figure 36 3A1705E 49...
Page 93: ...Dimensions Dimensions Top View Figure 43 Side View Figure 44 3A1705E 93...
Page 95: ...Dimensions Pallet Mounting Dimensions Figure 48 3A1705E 95...
Page 97: ...Notes Notes 3A1705E 97...