16 824-000
Intermediate Problem Solving
TYPE OF PROBLEM
WHAT TO CHECK
If check is OK, go to next check
WHAT TO DO
When check is not OK, refer to this column
Spray Pattern Variations
1. Spray tip worn beyond sprayer pressure capa-
bility.
1. Replace spray tip.
NOTE: A smaller size tip will provide
longer life.
2. Check transducer (29) for wear or damage.
2. Replace transducer. See page 30.
3. Check pressure control (64) for smooth opera-
tion.
3. Replace pressure control. See page 29.
4. Check Low output section, page 15.
Motor Is Hot and Runs
Intermittently
1. Determine if sprayer was operated at high pres-
sure with small tips, which causes excessive
heat build up.
1. Decrease pressure setting or increase tip
size.
2. Be sure ambient temperature where sprayer is
located is no more than 90
F (32
C) and
sprayer is not located in direct sun.
2. Move sprayer to shaded, cooler area if
possible.
3. Check motor.
3. Replace motor. See page 25.
Building Circuit Breaker
Opens As Soon As Sprayer
Switch Is Turned On.
1. Check all electrical wiring for damaged insula-
tion, and all terminals for loose fit or damage.
Also check wires between pressure control and
motor. See page 25.
1. Repair or replace any damaged wiring or
terminals. Securely reconnect all wires.
2. Check for missing motor brush inspection plate
gasket (see page 17), bent terminal forks or
other metal to metal contact points which could
cause a short.
2. Correct faulty conditions.
3. Check motor armature for shorts. Use an arma-
ture tester (growler) or perform motor test. See
page 17. Inspect windings for burns.
3. Replace motor. See page 25.
4. Check motor start board (47) by substituting
with a good board.
CAUTION: Do not perform this check until
motor armature is determined to be good. A
bad motor armature can burn out a good board.
4. Replace board. See page 26.
Circuit breaker opens after
sprayer operates for 5 to 10
minutes.
1. Check ‘Basic Problems – Electrical’ on page
13.
Building circuit breaker
opens as soon as sprayer
is plugged into outlet and
sprayer is NOT turned on.
1. Check ON/OFF switch (52).
Be sure sprayer is
unplugged! Disconnect wires from switch.
Check switch with ohmmeter. The reading
should be infinity with ON/OFF switch OFF,
and zero with switch ON.
CAUTION: A short in motor circuit can damage
switch and or motor start board (47).
1. Replace ON/OFF switch. See page 26.
2. Check electrical supply with volt meter. Meter
should read 105–125 VAC.
2. If voltage is too high, do not operate
sprayer until corrected.
Unit will not run on gener-
ator but does run on AC
power
Check the generator’s peak voltage. This sprayer will
not run if the peak voltage is above 190V.
Use AC power or a different generator