Appendix D - ADM Event and Error Codes Overview
313873J
79
WMC6
Red Tank
Con. Fault
Unexpected current to relay 1
Alarm
Shorted module
If temperature is being affected by a zone that has
been disabled, replace heat module
WMC5
Blue Tank
Con. Fault
Alarm
WMC3
Red Inline
Con. Fault
Alarm
WMC1
Blue Inline
Con. Fault
Alarm
WMC2
Red Hose
Con. Fault
Alarm
WMC4
Blue Hose
Con. Fault
Alarm
WMC7
Red Chiller
Con. Fault
Alarm
WMC8
Blue Chiller
Con. Fault
Alarm
WMH1
Motor
Controller
Fault
A general fault has occurred
within the MCM
Deviation Internal hardware failure
Cycle power, if the error persists the MCM will need to
be replaced
WSC0
Invalid
Setpoint
Request
The requested controlling
value (pressure or flow) is
outside the limits of the system
Deviation
System incorrectly setup
On the ADM go into the setup screens -> System->
and ensure that all pages have properly defined
values
Shot incorrectly defined
Redefine shot with control parameters within the limits
of the system
WSD0
Invalid Gel
Timer
Definition
The shot that was entered for
the gel timer is not a valid shot.
This must be fixed before the
gel timer will function properly
Deviation
Gel timer shot is below
the minimum dispense
amount or set for a
invalid pressure/flow
Select a different shot or modify existing shot data
The MCM has
determined that the gel
timer shot will not be able
to be executed based
parameters entered in
the ADM
If you are certain that the shot is within parameters,
try running the Learn Mode routine found in the setup
screen Calibration. If the error persists, a gel shot with
reduced control parameters is required.
Error
Code
Error Name
Error Description
Error
Type
Cause
Solution