7. Additional function of the KLplus/KL24plus and KLbasic/KL24base control unit
35 / 54
Connecting a contactor to switch the compressor
7.3.2
If the inbuilt compressor has a power consumption in excess of 6 A, a contactor for controlling
the compressor is also fitted in the cabinet. The switching status of the contactor is monitored
via the contactor monitoring input X4.
Connecting a UV reactor
7.3.3
A downstream UV reactor can be connected to the control unit via the connection (X3 / ST8).
Consult the installation instructions for the UV module for more details.
Phosphate precipitation with metering pump
Precipitant
Please note:
Iron(III)chloride is harmful if swallowed and is irritating to skin.
There is a risk of serious damage to eyes.
There is a danger of explosion if the product comes into contact with alkali met-
als, allyl chloride or ethylene oxide.
Please read the accompanying safety data sheet before using phosphate
precipitants!
Wear protective clothing when handling iron(III)chloride.
Keep precipitant containers out of the reach of children and unauthorised per-
sons.
A phosphate metering pump can be connected to the control unit via the connection (X3 / ST5).