8
.
Fault messages and rectification
30 / 40
Unusual water levels - troubleshooting
8.2
Observation
Possible cause
Corrective action
The water level in the
aeration tank is unu-
sually high.
Plant is running in holiday mode.
Plant is constantly running in cycle
pause.
Control settings are incorrect.
The outflow lifter is congested.
The air hose to the outflow lifter is
leaking.
Flooding in the receiving water
course doesn't allow water to drain
from plant.
Controller is defective.
Ending of holiday mode
Have the controller settings
checked by service technician
Have SBR reactor pumped out
and clean lifter
Have SBR reactor pumped out
and seal hose connections
Wait until flooding subsides,
Contact maintenance company
The plant emits
odours, the treated
wastewater is cloudy
or discoloured
Too little air is supplied to the plant
One-sided aeration due to defective
membrane unit
Have aeration time increased by
service company
Verify aeration diagram, contact
maintenance company
Aeration diagram is
one-sided and large,
isolated bubbles are
rising
Membrane unit defective
Aerator unit is leaking
Aerator unit is not positioned correctly
on the bottom
Contact maintenance company
Contact maintenance company
Possible faults at the air distributor (valve block)
8.3
Observation
Possible cause
Anchor does not pick up.
Supply voltage is interrupted or insufficient.
Motor defective!
Anchor blocked in polluted tube space.
Valve does not close.
Anchor blocked!
No power supply
Valve does not open.
Nominal voltage is not present
Status: 12 / 2017
Specifications subject to change without notice!
Summary of Contents for one2clean+ XXL
Page 39: ...13 Notes 39 40 13 Notes ...