27
Computer: QGS<cr>
UPS: (220.2 50.0 220.0 50.0 027.0 100 345.8 344.9 241.0 241.5 045.0 100011000000<cr>
Means:
I/P voltage is 220.2V.
I/P frequency is 50.0Hz
O/P voltage is 220.0V
O/P frequency is 50.0Hz.
O/P current is 27.0A
O/P load 100%
Positive BUS voltage is 345.8V
Negative BUS voltage is 344.9V
P Battery voltage is 241.0V.
N Battery voltage is 241.5V.
Temperature is 45.0 degrees of centigrade.
On-line mode, Utility OK, Bypass Active, UPS failed.
9.2.2 V<n>
This command is to set the nominal output voltage. The format is:
Computer: V<n><Enter>
UPS: (ACK or (NAK*
*: If UPS accepts this command, responds ACK. Otherwise, responds NAK
Output Voltage: <n>. n is 208,220,230,240.
Default status: Nominal output voltage 220V. (It can be set only in bypass mode)
For example:
Computer: V230<Enter>
UPS: (ACK
Meanings: set output nominal voltage to 230V.
9.2.3 V±<n>
This command is to adjust the nominal inverter voltage. The format is:
Computer: V±<n><Enter>
UPS: (ACK or (NAK*
*: If UPS accepts this command, responds ACK. Otherwise, responds NAK
Voltage adjust step: <n>. n=00, 0
1……, 99.
For example:
Computer: V+01<Enter>
UPS: (ACK
Meanings: Inverter voltage will increase about 0.1Volt.
9.2.4 BUSP±<n>
This command is to adjust the positive BUS voltage, the format is:
Computer: BUSP±<n><Enter>