Working setpoint and configuration parameters 

 

PARAM. 

MIN. 

MAX.  

U.M.  

DEF. 

GRAM FG 

HAV 

GRAM KG 

HAV 

GRAM FG 

FAV 

GRAM KG 

FAV 

WORKING SETPOINT 

 SP  

r1  

 r2  

 °C/°F (1)  

‐18 

‐18 

 working setpoint; see also r0 and r12  

PARAM. 

MIN. 

MAX.  

U.M.  

DEF. 

GRAM FG 

HAV 

GRAM KG 

HAV 

GRAM FG 

FAV 

GRAM KG 

FAV 

ANALOG INPUTS 

CA1  

‐25 

25 

°C/°F (1)  

if P4 = 0, 1 or 2, room probe offset  
if P4 = 3, incoming air probe offset  

CA2  

‐25 

25 

°C/°F (1)  

evaporator probe offset  

CA3  

‐25 

25 

°C/°F (1)  

if P4 = 1, condenser probe offset  
if P4 = 2, critical temperature probe offset  
if P4 = 3, outgoing air probe offset  

P0  

‐ ‐  

probe type  
0 = PTC  
1 = NTC  

P1  

‐‐ 

degree Celsius decimal point (during normal operation)  
1 = YES  

P2  

‐ ‐  

unit of measurement for temperature (2)  
0 = °C (Celsius degree; resolution depends on P1 parameter)  
1 = °F (Fahrenheit degree; resolution is 1 °F)  

P3  

‐ ‐  

evaporator probe function  
0 = absent probe  
1 = defrost probe and probe determining the activity of the evaporator fan  
2 = probe determining the activity of the evaporator fan  

P4  

‐ ‐  

fourth inlet function  
0 = multifunction input (digital input)  
1 = condenser probe (analog input )  
2 = critical temperature probe (analog input )  
3 = outlet air probe (analog input ) (3)  

P5  

‐‐ 

magnitude displayed during normal operation  
0 = if P4 = 0, 1 or 2, room temperature  
      if P4 = 3, CPT temperature 
1 = working setpoint  
2 = evaporator temperature   
3 =  if P4 = 0, “‐ ‐ ‐”  
       if P4 = 1, condenser temperature  
       if P4 = 2, critical temperature  
       if P4 = 3, outlet air temperature  
4 = if P4 = 0, 1 o 2, “‐ ‐ ‐”  
       if P4 = 3, inlet air temperature  

P7  

100 

%  

50 

50 

50 

50 

50 

inflowing air temperature percentage for the calculation of the CPT temperature  

P8   

250 

0,1 s  

100 

100 

100 

100 

delayed display of temperature changes as detected by the probes   

PARAM. 

MIN. 

MAX. 

 U.M. 

DEF. 

GRAM FG 

HAV 

GRAM KG 

HAV 

GRAM FG 

FAV 

GRAM KG 

FAV 

MAIN REGULATOR 

r0  

0,1 

15 

°C/°F (1)  

working setpoint differential; see also r12  

r1  

‐99 

r2  

°C/°F (1)  

‐40 

‐20 

‐20 

minimum working setpoint  

r2  

r1  

99 

°C/°F (1)  

50 

‐10 

12 

‐10 

12 

maximum working setpoint  

r4  

99 

°C/°F (1)  

working setpoint increase during the “energy saving" function; see also i5, i10 and HE2  

r5  

‐‐ 

cooling or heating operation (4)  
0 = cooling  
1 = heating  

r6  

99 

°C/°F (1)  

if r5 = 0, working setpoint decrease during the “rapid cooling” function (only if r8 = 1); see also r7  
if r5 = 1, working setpoint increase during the “rapid heating” function (only if r8 = 1); see also r7  

r7  

240 

min  

30 

if r5 = 0, “rapid cooling” function duration (only if r8 = 1); see also r6  
if r5 = 1, “rapid heating” function duration (only if r8 = 1); see also r6  

r8  

‐‐ 

this function can be enabled / disabled with the key FNC 

V

  

0 = none  
1 = if r5 = 0, “Rapid cooling” function  
      if r5 = 1, “Rapid heating” function  
2 = “energy saving” function (only if r5 = 0)  

r12   

 ‐‐‐ 

working setpoint differential type  
0 = asymmetric  
1 = symmetric  

PARAM. 

MIN. 

MAX.  

U.M.  

DEF.  

GRAM FG 

HAV 

GRAM KG 

HAV 

GRAM FG 

FAV 

GRAM KG 

FAV 

COMPRESSOR PROTECTION SYSTEM  

C0  

240 

 min  

delay in switching on of compressor after the device switches on (5)  

C2  

240 

min  

minimum compressor switch‐off duration (6)  

C3  

240 

s  

180 

180 

180 

180 

minimum duration of compressor switch on time  

Summary of Contents for Eco Euro KG 60

Page 1: ...765041996 Rev 001 1 Operating and servicemanual Eco Midi KG FG 60 82...

Page 2: ...g the product 3 Temperature setting 4 Keyboard lock 4 Alarms 5 Error codes on the display 6 Defrosting 7 Setting the configuration parameters 8 Manufacturer s settings 9 Working setpoint and configura...

Page 3: ...this is indicated by a small control lamp which is the only one lit in the lower right corner of the display To switch the product on press for approx 3 seconds During start up the control lamp will b...

Page 4: ...mpressor is running Alternatively by not touching the keys for a minimum of 15 seconds the controls will switch back to the normal temperature display and the value that has been set will be saved aut...

Page 5: ...is shown in the display if the condenser temperature has been too high Clean the condenser filter in front of the condenser Refer to the placement of the filter in Fig 3 CSd Compressor shut off This...

Page 6: ...Control lamp for defrosting Lit continuously during defrosting Blinks while draining after completed defrosting Control lamp for evaporator fan Lit continuously when the evaporator fan is in operatio...

Page 7: ...ng is automatically performed 4 times every 24 hours by a defrost heating element Manual defrosting If the cabinet is operating under severe load frequent door opening and frequent replenishment manua...

Page 8: ...765041996 Rev 001 8 Setting the configuration parameters...

Page 9: ...765041996 Rev 001 9 Manufacturer s settings...

Page 10: ...t air temperature 4 if P4 0 1 o 2 if P4 3 inlet air temperature P7 0 100 50 50 50 50 50 inflowing air temperature percentage for the calculation of the CPT temperature P8 0 250 0 1 s S 100 100 100 100...

Page 11: ...d16 0 evaporator fan activity will depend on F2 parameter if d16 0 the evaporator fan shall remain off d8 0 3 0 0 0 0 0 defrost activation methods 0 AT INTERVALS FOR TIME defrost will be activated on...

Page 12: ...aporator fan operation when the compressor is turned off see also F7 only if F0 2 PARAM MIN MAX U M DEF GRAM FG HAV GRAM KG HAV GRAM FG FAV GRAM KG FAV DIGITAL INPUTS i0 0 5 5 2 2 2 2 effect caused by...

Page 13: ...w consumption function is activated 0 the mode shall never be aactivated PARAM MIN MAX U M DEF GRAM FG HAV GRAM KG HAV GRAM FG FAV GRAM KG FAV VARIOUS key activation POF 0 1 1 1 1 1 1 1 YES PAS 99 999...

Page 14: ...condenser temperature falls below the value set with parameter F11 provided that the compressor is switched off 22 the compressor is switched off 10 s after the activation of the input if the input i...

Page 15: ...765041996 Rev 001 15 Wiring diagram...

Reviews: