6.0 FURNACE OPERATION AND SETTINGS
SHUTTING FURNACE DOWN
POWER OFF
Turn off main power breaker or disconnect.
FUEL OFF
Shut off manual fuel supply valve.
Always keep manual fuel supply valve shut off if the burner is shut down for an extended
period.
RESTARTING FURNACE
Follow this procedure before restarting a unit that has been shut down for an extended period.
INSPECTION
Have the furnace/system serviced and inspected by a
qualified technician
.
FUEL
Turn on fuel supply and check that there are no leaks.
POWER
Turn on power and check that the furnace starts and operates as usual.
OPERATION
If the furnace/system fails to operate or operates in an unusual manner, call
your service technician. If the burner fails to operate at any time, call a
qualified burner technician.
6.1 BLOWER SETTING
Ensure power is off when adjusting blower setting
. For heating, use the blower speeds shown
on the furnace specifications to give a temperature rise according to the technical information tables
on page 18 (KLR) and 19 (KLF). The Lo blower speed can be used for air circulation when heating
or cooling are not required. Set blower speeds to match the installation requirements.
FAN & LIMIT CONTROL
Limit
185°F – Factory set
Fan On
45 seconds after the burner starts
Fan Off
Adjustable on ST9103 board (see page 18)
6.2 FAN TIMER CONTROL BOARD (ST9103A1028)
o “FAN OFF” Dip Switches adjustment
Dip Switches
Summary of Contents for KLF-100
Page 7: ...7 KLR 200 DIMENSIONS Dimensions are in inches KLF 100 DIMENSIONS Dimensions are in inches...
Page 22: ...22 Position of the ST9103A1028 Electronic Board KLR 100 and 200 KLF 100 KLF 200...
Page 28: ...28 8 0 ELECTRICAL WIRING DIAGRAMS HEATING COOLING KLR KLF RIELLO...
Page 29: ...29 HEATING COOLING For more informations see next page...
Page 30: ...30 GeniSys control schematic with the ST9103 Board...
Page 31: ...31 HEATING ONLY RIELLO BECKETT...
Page 34: ...34 KLR 200 EXPLODED PARTS VIEW Detail A ELB A0 0008 00 Electric box...