24
Step
Possible Cause
Check-out procedure
Corrective action
No Heat
5
Riello burner
Check for 120 Volts on
the black wire, contact
(COM) on the burner
activation relay
Check if oil primary
control is on reset
Check for continuity
between the two wires
yellow and violet on
the burner activation
relay
Check for 120 Volts on
the contact (No) of the
burner activation relay
Check for 120 volts on the
orange wire coming to the
burner (L)
Yes - Move to next step
No - Back to step # 4 or check for
bad connection
Yes - Press reset button
No - Move to the next step
Yes - Move to next step
No - Change the electronic fan control
Yes - Move to next step
No - Change the burner activation relay
Yes - Failure on the burner
No - Change the electronic fan control
Beckett Burner
Check for 120 Volts on
terminal strip (COM) of the
burner activation relay
Check if oil primary control
is on Reset and by-pass
on (TT)
Check for continuity
between the two wires
yellow and violet on
the burner activation
relay
Check for 120 Volts on the
contact (NO) on the burner
activation relay
Check for 120 Volts on the
orange wire coming to the
burner
Yes - Move to next step
No - Back to step # 4 or check bad
connection
Yes - Press reset button, check
by- pass on (TT)
No - Move to the next step
Yes - Move to next step
No - Change the electronic fan control
Yes - Move to next step
No - Change the burner activation relay
Yes - Failure on the burner
No - Change the primary control
Summary of Contents for KLF-100
Page 7: ...7 KLR 200 DIMENSIONS Dimensions are in inches KLF 100 DIMENSIONS Dimensions are in inches...
Page 22: ...22 Position of the ST9103A1028 Electronic Board KLR 100 and 200 KLF 100 KLF 200...
Page 28: ...28 8 0 ELECTRICAL WIRING DIAGRAMS HEATING COOLING KLR KLF RIELLO...
Page 29: ...29 HEATING COOLING For more informations see next page...
Page 30: ...30 GeniSys control schematic with the ST9103 Board...
Page 31: ...31 HEATING ONLY RIELLO BECKETT...
Page 34: ...34 KLR 200 EXPLODED PARTS VIEW Detail A ELB A0 0008 00 Electric box...