background image

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pump

12

428 01 5301 05

Specifications subject to change without notice.

START

UP PROCEDURE

1. Set indoor thermostat selector switch to OFF.

2. Turn ON all electrical disconnect devices.

3. If unit has a crankcase heater, energize the heater

and wait 24 hours before proceeding.

4. Set indoor thermostat at desired temperature.  Be

sure setpoint is below indoor ambient temperature

to call for cooling, or above indoor ambient to call

for heating.

5. Set indoor thermostat selector switch to COOL or

HEAT. Operate unit for minimum 15 minutes, then

check the system refrigerant charge.

REFRIGERANT CHARGE

Factory charge amount and desired subcooling are

shown on unit rating plate. Charging method is shown on

information plate inside unit. Additional subcooling may

be required to achieve optimal heating performance

based on installed indoor unit. (see figure 16)
For TXV, use subcooling method.
For Piston, use superheat method.
To properly check or adjust charge, conditions must be

favorable for subcooling or superheat charging.

Favorable conditions exist when the outdoor temperature

is between 70

_

F and 100

_

F (21

_

C and 38

_

C), and the

indoor temperature is between 70

_

F and 80

_

F (21

_

C and

27

_

C). 

 

Follow the procedure below.

Unit is factory charged for 15 feet (4.6m) of lineset. Adjust

charge by adding or removing 0.6 oz/ft (17 g/mm) of 3/8

liquid line above or below 15 feet (4.6 m) respectively.
For standard refrigerant line lengths 80 feet (24.4m) or

less, allow system to operate in cooling mode at least 15

minutes. If conditions are favorable, check system

charge by super heat method for fixed metering device

and subcooling method for TXV. If any adjustment is

necessary, adjust charge slowly and allow system to

operate for 15 minutes to stabilize before declaring a

properly charged system. Refer to figure 16 for additional

subcooling required.
If the indoor temperature is above 80

_

F (27

_

C), and the

outdoor temperature is in the favorable range, adjust

system charge by weight based on line length and allow

the indoor temperature to drop to 80

_

F (27

_

C) before

attempting to check system charge by subcooling method

as described above.
If the indoor temperature is below 70

_

F (21

_

C), or the

outdoor temperature is not in the favorable range, adjust

charge for line set length above or below 15 feet (4.6m)

only. Charge level should then be appropriate for the

system to achieve rated capacity. The charge level could

then be checked at another time when the both indoor and

outdoor temperatures are in a more favorable range.

NOTE:

 If line length is beyond 80 feet (24.4m) or greater

than 20 feet (6.1m) vertical separation,  See Long Line

Guideline for special charging requirements.

A. UNITS WITH COOLING MODE TXV

Units installed with cooling mode TXV require charging by

the subcooling method.

1. Operate unit a minimum of 15 minutes before

checking charge.

NOTE:

 If outdoor unit has a 2

speed fan motor,

motor will operate in low speed when outdoor

ambient temperature is below 82

_

F (28

_

C).  Pull

the BRN/YEL low voltage wire off the fan control

and the unit will default to high speed fan for

servicing. Reconnect wire after servicing.

2. Measure liquid service valve pressure by attaching

an accurate gage to service port.

3. Measure liquid line temperature by attaching an

accurate thermistor type or electronic

thermometer to liquid line near outdoor coil.

4. Refer to unit rating plate for required subcooling

temperature.

5. Refer to figure 15. Find the point where required

subcooling temperature intersects measured

liquid service valve pressure.

6. To obtain required subcooling temperature at a

specific liquid line pressure, add refrigerant if liquid

line temperature is higher than indicated or reclaim

refrigerant if temperature is lower. Allow a

tolerance of 

"

3

_

F (

|

1.7

_

C).

B. UNITS WITH INDOOR PISTON

Units installed with indoor pistons require charging by the

superheat method.
The following procedure is valid when indoor airflow is

within 

"

21 percent of its rated CFM.

1. Operate unit a minimum of 15 minutes before

checking charge.

2. Measure suction pressure by attaching an

accurate gage to suction valve service port.

3. Measure suction temperature by attaching an

accurate thermistor type or electronic

thermometer to suction line at service valve.

4. Measure outdoor air dry

bulb temperature with

thermometer.

5. Measure indoor air (entering indoor coil) wet

bulb

temperature with a sling psychrometer.

6. Refer to figure 13. Find outdoor temperature and

evaporator entering air wet

bulb temperature. At

this intersection, note superheat.  Where a dash

(

−−

) appears on the table, do not attempt to charge

system under these conditions or refrigerant

slugging may occur.  Charge must be weighted in,

adding or removing 0.6 oz/ft of 3/8 liquid line above

or below 15 feet (4.6m) respectively.

7. Refer to figure 14. Find superheat temperature

(from #6 above) and suction pressure. At this

intersection, note suction line temperature.

8. If unit has a higher suction line temperature than

charted temperature, add refrigerant until charted

temperature is reached.

9. If unit has a lower suction line temperature than

charted temperature, reclaim refrigerant until

charted temperature is reached.

10. When adding refrigerant, charge in liquid form into

suction service port using a flow

restricting

device.

Summary of Contents for R4H3 Series

Page 1: ...e following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on p...

Page 2: ...r intakes vents or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the un...

Page 3: ...1 4 540 26x26 660x660 31 1 8x31 1 8 791x791 9 1 16 230 6 1 2 165 24 5 8 625 31 1 2x31 1 2 800x800 C FASTENING UNIT DOWN If conditions or local codes require the unit be attached in place remove the k...

Page 4: ...ine Applications Guideline for line set sizing NOTE Total line set length must not exceed 200 feet 61m NOTE A crankcase heater must be used when the refrigerant line length exceeds 80 feet 24 4m If ou...

Page 5: ...operation Do not bury more than 36 1m of line set under ground Refrigerant may migrate to cooler buried section during extended periods of unit shut down causing refrigerant slugging and possible com...

Page 6: ...efer to Figure 5 Replace valve core when brazing is completed WARNING FIRE HAZARD Failure to remove refrigerant and oil charge before brazing could result in personal injury death and or property dama...

Page 7: ...ur During this time dry nitrogen will diffuse throughout the system absorbing moisture 5 Repeat this procedure as indicated in Figure 7 6 After the final evacuate sequence confirm there are no leaks i...

Page 8: ...e panel or a properly driven and electrically grounded ground rod Wiring Connections Make all outdoor electrical supply Line Voltage connections with raintight conduit and fittings Most codes require...

Page 9: ...DOOR FAN COIL WHEN INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W 3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2...

Page 10: ...circuit and operation of the defrost thermostat itself will not be observed Skip to 3 2 Use a volt meter to confirm there is no voltage across the DFT leads 24 volts across the SFT terminals indicates...

Page 11: ...ithout notice Figure 12 Defrost Control Board R8 OF1 K1 O1 R21 C2 R6 H9C1 C US R14 R13 D13 R7 C4 C10 JW2 JW1 D3 C16 C7 R28 D6 JW3 C13 R4 R1 R2 R3 R11 R5 R26 D1 D2 D10 A29 R9 D4 C19 C9 C1 OF2 CEBD43052...

Page 12: ...range NOTE If line length is beyond 80 feet 24 4m or greater than 20 feet 6 1m vertical separation See Long Line Guideline for special charging requirements A UNITS WITH COOLING MODE TXV Units install...

Page 13: ...34 37 24 3 5 7 8 10 12 13 16 17 19 21 80 5 8 12 15 18 21 25 28 31 35 27 3 4 7 8 10 12 14 16 17 19 85 8 11 15 19 22 26 30 33 29 4 6 8 11 12 14 17 18 90 5 9 13 16 20 24 27 31 32 3 5 7 9 11 13 15 17 95 6...

Page 14: ...26 299 90 32 88 31 86 30 84 29 82 28 80 27 308 92 33 90 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88...

Page 15: ...3 FS M U 4P24 A TXV 5 3 ED 4X30 EA 4X30 14 17 A 3 EN 4X30 3 3 EHD4X30A 3 3 FEM4 P X 30 A TXV 3 FSA4X30 A 3 FEA4X30 A 3 FXM4X30 A 5 5 FS M U 4P30 A TXV 5 5 FVM FCM 4X36 5 3 ED 4X36 EA 4X36 14 17 21 A 5...

Page 16: ...cer bringing on the first bank supplemental electric heat and providing electrical potential to the second heater sequencer if used If outdoor temperature falls below the setting of the outdoor thermo...

Page 17: ...ith other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not i...

Reviews: