background image

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pump

428 01 5301 05

13

Specifications subject to change without notice.

11. If outdoor air temperature or pressure at suction

valve changes, charge to new suction line

temperature indicated on chart.

12. Optimum performance will be achieved when

the operating charge produces 5

_

 to 6

_

F

suction superheat at suction service valve

with 82

_

F (28

_

C) outdoor ambient and 80

_

F

(27

_

C) dry bulb (67

_

F / 19

_

C) wet bulb) indoor

temperature (DOE “B” test conditions) at rated

airflow.

C. HEATING MODE

To check system operation during heating cycle, refer to

the Tech Label on outdoor unit. This chart indicates

whether a correct relationship exists between system

operating pressure and air temperature entering indoor

and outdoor units. If pressure and temperature do not

match on chart, system refrigerant charge may not be

correct. Do not use chart to adjust refrigerant charge.

NOTE:

 When charging is necessary during heating

season, charge must be weighed in accordance with unit

rating plate 

0.6 ounces per foot of 

a

 inch liquid line above

or below 15 feet respectively (

17g per 305mm of 10mm

liquid line above or below 4.6m respectively).

Figure 13

SUPERHEAT CHARGING TABLE ˚F

SUPERHEAT CHARGING TABLE ˚C

EVAPORATOR ENTEREING AIR ˚F AT WB

EVAPORATOR ENTEREING AIR ˚C AT WB

 ˚F

50 52 54 56 58 60 62 64 66 68 70 72 74 76

 ˚C

10 11 12 13 14 16 17 18 19 20 21 22 23 24

Outdoor

Temp

SUPERHEAT ˚F AT LOW­SIDE SERVICE PORT

Outdoor

Temp

SUPERHEAT ˚C AT LOW­SIDE SERVICE PORT

55

9 12 14 17 20 23 26 29 32 35 37 40 42 45

13

5 7 8 9 11 13 14 16 18 19 21 22 23 25

60

7 10 12 15 18 21 24 27 30 33 35 38 40 43

16

4 6 7 8 10 12 13 15 17 18 19 21 22 24

65

­

6 10 13 16 19 21 24 27 30 33 36 38 41

18

­

3 6 7 9 11 12 13 15 17 18 20 21 23

70

­

­

7 10 13 16 19 21 24 27 30 33 36 39

21

­

­

4 6 7 9 11 12 13 15 17 18 20 22

75

­

­

­

6 9 12 15 18 21 24 28 31 34 37

24

­

­

­

3 5 7 8 10 12 13 16 17 19 21

80

­

­

­

­

5 8 12 15 18 21 25 28 31 35

27

­

­

­

­

3 4 7 8 10 12 14 16 17 19

85

­

­

­

­

­

­

8 11 15 19 22 26 30 33

29

­

­

­

­

­

­

4 6 8 11 12 14 17 18

90

­

­

­

­

­

­

5 9 13 16 20 24 27 31

32

­

­

­

­

­

­

3 5 7 9 11 13 15 17

95

­

­

­

­

­

­

­

6 10 14 18 22 25 29

35

­

­

­

­

­

­

­

3 6 8 10 12 14 16

100

­

­

­

­

­

­

­

­

8 12 15 20 23 27

38

­

­

­

­

­

­

­

­

4 7 8 11 13 15

105

­

­

­

­

­

­

­

­

5 9 13 17 22 26

41

­

­

­

­

­

­

­

­

3 5 7 9 12 14

110

­

­

­

­

­

­

­

­

­

6 11 15 20 25

43

­

­

­

­

­

­

­

­

­

3 6 8 11 14

115

­

­

­

­

­

­

­

­

­

­

8 14 18 23

46

­

­

­

­

­

­

­

­

­

­

4 8 10 13

*Optimum performance point, 82°F (28°C) outdoor ambient and (80°F / 27°C dry bulb), (67°F / 19°C wet bulb) indoor conditions. (DOE B Test
Conditions)

 Where a dash (-) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be
weighed in.

Note

: Superheat °F is at low-side service port, Allow a tolerance of ± 3°F (± 1.7°C)

Note

: Indoor dry bulb between 70°F and 80°F (21°C and 27°C)

Figure

14

SUCTION PRESSURE AT SERVICE PORT PSIG

SUCTION PRESSURE AT SERVICE PORT kPA

SUPER-

HEAT

TEMP 

˚F

108

112

117

121

126

131

139

141

146

SUPER-

HEAT

TEMP 

˚C

743

774

805

836

869

902

957

971 1005

REQUIRED SUCTION TUBE TEMPERATURE 

˚F

(MEASURED AT LOW-SIDE SERVICE PORT)

REQUIRED SUCTION TUBE TEMPERATURE 

˚C

(MEASURED AT LOW-SIDE SERVICE PORT)

0

35

37

39

41

43

45

47

49

51

0

2

3

4

5

6

7

8

9

11

2

37

39

41

43

45

47

49

51

53

1

3

4

5

6

7

8

9

11

12

4

39

41

43

45

47

49

51

53

55

2

4

5

6

7

8

9

11

12

13

6

41

43

45

47

49

51

53

55

57

3

5

6

7

8

9

11

12

13

14

8

43

45

47

49

51

53

55

57

59

4

6

7

8

9

11

12

13

14

15

10

45

47

49

51

53

55

57

59

61

6

7

8

9

11

12

13

14

15

16

12

47

49

51

53

55

57

59

61

63

7

8

9

11

12

13

14

15

16

17

14

49

51

53

55

57

59

61

63

65

8

9

11

12

13

14

15

16

17

18

16

51

53

55

57

59

61

63

65

67

9

11

12

13

14

15

16

17

18

19

18

53

55

57

59

61

63

65

67

69

10

12

13

14

15

16

17

18

19

21

20

55

57

59

61

63

65

67

69

71

11

13

14

15

16

17

18

19

21

22

22

57

59

61

63

65

67

69

71

73

12

14

15

16

17

18

19

21

22

23

24

59

61

63

65

67

69

71

73

75

13

15

16

17

18

19

21

22

23

24

26

61

63

65

67

69

71

73

75

77

14

16

17

18

19

21

22

23

24

25

28

63

65

67

69

71

73

75

77

79

16

17

18

19

21

22

23

24

25

26

30

65

67

69

71

73

75

77

79

81

17

18

19

21

22

23

24

25

26

27

Summary of Contents for R4H3 Series

Page 1: ...e following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on p...

Page 2: ...r intakes vents or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the un...

Page 3: ...1 4 540 26x26 660x660 31 1 8x31 1 8 791x791 9 1 16 230 6 1 2 165 24 5 8 625 31 1 2x31 1 2 800x800 C FASTENING UNIT DOWN If conditions or local codes require the unit be attached in place remove the k...

Page 4: ...ine Applications Guideline for line set sizing NOTE Total line set length must not exceed 200 feet 61m NOTE A crankcase heater must be used when the refrigerant line length exceeds 80 feet 24 4m If ou...

Page 5: ...operation Do not bury more than 36 1m of line set under ground Refrigerant may migrate to cooler buried section during extended periods of unit shut down causing refrigerant slugging and possible com...

Page 6: ...efer to Figure 5 Replace valve core when brazing is completed WARNING FIRE HAZARD Failure to remove refrigerant and oil charge before brazing could result in personal injury death and or property dama...

Page 7: ...ur During this time dry nitrogen will diffuse throughout the system absorbing moisture 5 Repeat this procedure as indicated in Figure 7 6 After the final evacuate sequence confirm there are no leaks i...

Page 8: ...e panel or a properly driven and electrically grounded ground rod Wiring Connections Make all outdoor electrical supply Line Voltage connections with raintight conduit and fittings Most codes require...

Page 9: ...DOOR FAN COIL WHEN INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W 3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2...

Page 10: ...circuit and operation of the defrost thermostat itself will not be observed Skip to 3 2 Use a volt meter to confirm there is no voltage across the DFT leads 24 volts across the SFT terminals indicates...

Page 11: ...ithout notice Figure 12 Defrost Control Board R8 OF1 K1 O1 R21 C2 R6 H9C1 C US R14 R13 D13 R7 C4 C10 JW2 JW1 D3 C16 C7 R28 D6 JW3 C13 R4 R1 R2 R3 R11 R5 R26 D1 D2 D10 A29 R9 D4 C19 C9 C1 OF2 CEBD43052...

Page 12: ...range NOTE If line length is beyond 80 feet 24 4m or greater than 20 feet 6 1m vertical separation See Long Line Guideline for special charging requirements A UNITS WITH COOLING MODE TXV Units install...

Page 13: ...34 37 24 3 5 7 8 10 12 13 16 17 19 21 80 5 8 12 15 18 21 25 28 31 35 27 3 4 7 8 10 12 14 16 17 19 85 8 11 15 19 22 26 30 33 29 4 6 8 11 12 14 17 18 90 5 9 13 16 20 24 27 31 32 3 5 7 9 11 13 15 17 95 6...

Page 14: ...26 299 90 32 88 31 86 30 84 29 82 28 80 27 308 92 33 90 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88...

Page 15: ...3 FS M U 4P24 A TXV 5 3 ED 4X30 EA 4X30 14 17 A 3 EN 4X30 3 3 EHD4X30A 3 3 FEM4 P X 30 A TXV 3 FSA4X30 A 3 FEA4X30 A 3 FXM4X30 A 5 5 FS M U 4P30 A TXV 5 5 FVM FCM 4X36 5 3 ED 4X36 EA 4X36 14 17 21 A 5...

Page 16: ...cer bringing on the first bank supplemental electric heat and providing electrical potential to the second heater sequencer if used If outdoor temperature falls below the setting of the outdoor thermo...

Page 17: ...ith other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not i...

Reviews: