background image

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pump

16

428 01 5301 05

Specifications subject to change without notice.

SEQUENCE OF OPERATION

A. COOLING MODE

On a call for cooling, the thermostat makes circuits R

O,

R

Y, and R

G. Circuit R

O energizes reversing valve,

switching it to cooling position. Circuit R

Y energizes

contactor, starting outdoor fan motor and compressor.

Circuit R

G energizes indoor unit blower relay, starting

indoor blower motor.
When thermostat is satisfied, its contacts open,

de

energizing contactor and blower relay. Compressor

and motors stop.

NOTE:

 If indoor unit is equipped with a time

delay relay

circuit, the blower runs an additional length of time to

increase system efficiency. (Applies to both cooling and

heating modes.)

B. HEATING MODE

On a call for heating, the thermostat makes circuits R

Y

and R

G (circuit R

O is NOT made, and the reversing

valve stays in the de

energized, heating position). Circuit

R

Y energizes contactor, starting outdoor fan motor and

compressor. Circuit R

G energizes indoor blower relay,

starting blower motor. If the room temperature continues

to fall, circuit R

W2 is made through the second

stage

room thermostat bulb. Circuit R

W2 energizes a

sequencer, bringing on the first bank supplemental

electric heat and providing electrical potential to the

second heater sequencer (if used). If outdoor

temperature falls below the setting of the outdoor

thermostat (field

installed option), contacts close to

complete the circuit and bring on the second bank of

supplemental electric heat.
When the thermostat is satisfied, its contacts open,

de

energizing  contactor, blower relay, and sequencer.

Compressor, motors, and heaters stop.

MAINTENANCE

Condensate Drain

During the cooling season, check monthly for free flow of

drainage and clean if necessary.

Cleanliness

These tips will help keep the heat pump looking better and

working more efficiently:

1. Free flow of air is essential. Keep fences, shrubs,

trash cans, and other obstructions at least 18

inches (0.5m) from all coil inlets.

2. Keep the coil free of grass clippings, leaves,

weeds, and other debris.

NOTE:

 Coil may occasionally require cleaning with

a liquid solution. The coil must be cold when

cleaning. Use an alkaline based cleaner only.

Cleaning a hot coil or using an acid based cleaner

will remove the paint from the fins and may clog the

coil.

3. Never use a weather cover over the outdoor unit

unless it is a ventilated type or made of breathable

fabric that will allow moisture to evaporate rapidly.

A cover that holds moisture in the unit will cause

more rust build

up and damage than normal

exposure to weather.

Summary of Contents for R4H3 Series

Page 1: ...e following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on p...

Page 2: ...r intakes vents or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the un...

Page 3: ...1 4 540 26x26 660x660 31 1 8x31 1 8 791x791 9 1 16 230 6 1 2 165 24 5 8 625 31 1 2x31 1 2 800x800 C FASTENING UNIT DOWN If conditions or local codes require the unit be attached in place remove the k...

Page 4: ...ine Applications Guideline for line set sizing NOTE Total line set length must not exceed 200 feet 61m NOTE A crankcase heater must be used when the refrigerant line length exceeds 80 feet 24 4m If ou...

Page 5: ...operation Do not bury more than 36 1m of line set under ground Refrigerant may migrate to cooler buried section during extended periods of unit shut down causing refrigerant slugging and possible com...

Page 6: ...efer to Figure 5 Replace valve core when brazing is completed WARNING FIRE HAZARD Failure to remove refrigerant and oil charge before brazing could result in personal injury death and or property dama...

Page 7: ...ur During this time dry nitrogen will diffuse throughout the system absorbing moisture 5 Repeat this procedure as indicated in Figure 7 6 After the final evacuate sequence confirm there are no leaks i...

Page 8: ...e panel or a properly driven and electrically grounded ground rod Wiring Connections Make all outdoor electrical supply Line Voltage connections with raintight conduit and fittings Most codes require...

Page 9: ...DOOR FAN COIL WHEN INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W 3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2...

Page 10: ...circuit and operation of the defrost thermostat itself will not be observed Skip to 3 2 Use a volt meter to confirm there is no voltage across the DFT leads 24 volts across the SFT terminals indicates...

Page 11: ...ithout notice Figure 12 Defrost Control Board R8 OF1 K1 O1 R21 C2 R6 H9C1 C US R14 R13 D13 R7 C4 C10 JW2 JW1 D3 C16 C7 R28 D6 JW3 C13 R4 R1 R2 R3 R11 R5 R26 D1 D2 D10 A29 R9 D4 C19 C9 C1 OF2 CEBD43052...

Page 12: ...range NOTE If line length is beyond 80 feet 24 4m or greater than 20 feet 6 1m vertical separation See Long Line Guideline for special charging requirements A UNITS WITH COOLING MODE TXV Units install...

Page 13: ...34 37 24 3 5 7 8 10 12 13 16 17 19 21 80 5 8 12 15 18 21 25 28 31 35 27 3 4 7 8 10 12 14 16 17 19 85 8 11 15 19 22 26 30 33 29 4 6 8 11 12 14 17 18 90 5 9 13 16 20 24 27 31 32 3 5 7 9 11 13 15 17 95 6...

Page 14: ...26 299 90 32 88 31 86 30 84 29 82 28 80 27 308 92 33 90 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88...

Page 15: ...3 FS M U 4P24 A TXV 5 3 ED 4X30 EA 4X30 14 17 A 3 EN 4X30 3 3 EHD4X30A 3 3 FEM4 P X 30 A TXV 3 FSA4X30 A 3 FEA4X30 A 3 FXM4X30 A 5 5 FS M U 4P30 A TXV 5 5 FVM FCM 4X36 5 3 ED 4X36 EA 4X36 14 17 21 A 5...

Page 16: ...cer bringing on the first bank supplemental electric heat and providing electrical potential to the second heater sequencer if used If outdoor temperature falls below the setting of the outdoor thermo...

Page 17: ...ith other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not i...

Reviews: