background image

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pump

428 01 5301 05

3

Specifications subject to change without notice.

!

CAUTION

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property

damage.
Top surface of platform must be above estimated snow-

fall level to prevent snow blocking coil and to allow water

melt to drain from unit.

B. ROOF TOP INSTALLATION

This type of installation is not recommended on wood

frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level.

If installation is on a flat roof, locate unit minimum 6 inches

(152mm) above roof level.
Place the unit over one or more load bearing walls. If there

are several units, mount them on platforms that are

self

supporting and span several load bearing walls.

These suggestions are to minimize noise and vibration

transmission through the structure. If the structure is a

home or apartment, avoid locating the unit over

bedrooms or study.

NOTE:

 When unit is to be installed on a bonded

guaranteed roof, a release must be obtained from the

building owner to free the installer from all liabilities.

Figure 2

Tie Down Knockouts

Base

Pan

Depth

C

B

A

Base Pan Width

3/8” 

(10mm)

 dia. Tie Down Knockouts

In Base Pan (2 places)

View From Top

Inches (mm)

Base Pan Width x

Depth

Tie Down

Knockouts

Minimum

Mounting Pad

Dimensions

A

B

C

23x23

(584x584)

7

3/4

(197)

4

7/16

(113)

18

(457)

23x23

(584x584)

25

11/16x25

11/16

(652x652)

9

1/16

(230)

4

7/16

(113)

21

1/4

(540)

26x26

(660x660)

31

1/8x31

1/8

(791x791)

9

1/16

(230)

6

1/2

(165)

24

5/8

(625)

31

1/2x31

1/2

(800x800)

C. FASTENING UNIT DOWN

If conditions or local codes require the unit be attached in

place, remove the knockouts in the base pan and install

tie down bolts through the holes (refer to Figure 2).
Contact local distributor for hurricane hold

down details and

the P.E. (Professional Engineer) certification, when

required.

!

CAUTION

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property

damage.
Inadequate unit support may cause excessive vibration,

noise, and/or stress on the refrigerant lines, leading to re-

frigerant line failure.

REFRIGERATION SYSTEM

A. COMPONENT MATCHES

Check to see that the proper system components are in

place, especially the indoor coil.
R

410A  outdoor units can only be used with R

410A

specific indoor coils. If there is a refrigerant mis

match,

consult the indoor coil manufacturer to determine if a

refrigerant conversion kit is available for the indoor coil.
This outdoor unit is designed to achieve maximum

efficiency when used with indoor coils that utilize a TXV

refrigerant metering device or Piston with Teflon ring

metering device. If any other type of metering device is

installed on the indoor coil, consult the indoor coil

manufacturer to determine if a conversion kit is available.

Installing with TXV.

When installing a TXV on an indoor coil, follow the

instructions provided with the new TXV.
A typical TXV installation is shown in Figure 1.

Figure 1

Typical TXV Installation

TXV

SENSING

BULB

EQUALIZER

TUBE

INDOOR

COIL

SUCTION

TUBE

LIQUID

TUBE

SENSING BUL

STRAP

SUCTION TUBE

IN. OD & SMALLER

10 O’Clock

2 O’Clock

7/8

Summary of Contents for R4H3 Series

Page 1: ...e following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on p...

Page 2: ...r intakes vents or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the un...

Page 3: ...1 4 540 26x26 660x660 31 1 8x31 1 8 791x791 9 1 16 230 6 1 2 165 24 5 8 625 31 1 2x31 1 2 800x800 C FASTENING UNIT DOWN If conditions or local codes require the unit be attached in place remove the k...

Page 4: ...ine Applications Guideline for line set sizing NOTE Total line set length must not exceed 200 feet 61m NOTE A crankcase heater must be used when the refrigerant line length exceeds 80 feet 24 4m If ou...

Page 5: ...operation Do not bury more than 36 1m of line set under ground Refrigerant may migrate to cooler buried section during extended periods of unit shut down causing refrigerant slugging and possible com...

Page 6: ...efer to Figure 5 Replace valve core when brazing is completed WARNING FIRE HAZARD Failure to remove refrigerant and oil charge before brazing could result in personal injury death and or property dama...

Page 7: ...ur During this time dry nitrogen will diffuse throughout the system absorbing moisture 5 Repeat this procedure as indicated in Figure 7 6 After the final evacuate sequence confirm there are no leaks i...

Page 8: ...e panel or a properly driven and electrically grounded ground rod Wiring Connections Make all outdoor electrical supply Line Voltage connections with raintight conduit and fittings Most codes require...

Page 9: ...DOOR FAN COIL WHEN INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W 3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2...

Page 10: ...circuit and operation of the defrost thermostat itself will not be observed Skip to 3 2 Use a volt meter to confirm there is no voltage across the DFT leads 24 volts across the SFT terminals indicates...

Page 11: ...ithout notice Figure 12 Defrost Control Board R8 OF1 K1 O1 R21 C2 R6 H9C1 C US R14 R13 D13 R7 C4 C10 JW2 JW1 D3 C16 C7 R28 D6 JW3 C13 R4 R1 R2 R3 R11 R5 R26 D1 D2 D10 A29 R9 D4 C19 C9 C1 OF2 CEBD43052...

Page 12: ...range NOTE If line length is beyond 80 feet 24 4m or greater than 20 feet 6 1m vertical separation See Long Line Guideline for special charging requirements A UNITS WITH COOLING MODE TXV Units install...

Page 13: ...34 37 24 3 5 7 8 10 12 13 16 17 19 21 80 5 8 12 15 18 21 25 28 31 35 27 3 4 7 8 10 12 14 16 17 19 85 8 11 15 19 22 26 30 33 29 4 6 8 11 12 14 17 18 90 5 9 13 16 20 24 27 31 32 3 5 7 9 11 13 15 17 95 6...

Page 14: ...26 299 90 32 88 31 86 30 84 29 82 28 80 27 308 92 33 90 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88...

Page 15: ...3 FS M U 4P24 A TXV 5 3 ED 4X30 EA 4X30 14 17 A 3 EN 4X30 3 3 EHD4X30A 3 3 FEM4 P X 30 A TXV 3 FSA4X30 A 3 FEA4X30 A 3 FXM4X30 A 5 5 FS M U 4P30 A TXV 5 5 FVM FCM 4X36 5 3 ED 4X36 EA 4X36 14 17 21 A 5...

Page 16: ...cer bringing on the first bank supplemental electric heat and providing electrical potential to the second heater sequencer if used If outdoor temperature falls below the setting of the outdoor thermo...

Page 17: ...ith other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not i...

Reviews: