background image

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pump

4

428 01 5301 05

Specifications subject to change without notice.

Installing with Indoor Piston 

 cooling operation.

(Heat pumps also use an outdoor piston for heating

operation, refer to section F.)

Check piston size shipped with indoor unit to see if it

matches required indoor piston size shown on outdoor

unit rating plate.
If it does not match, replace indoor piston with 

cooling

piston, according to size marked on outdoor unit rating

plate.  (Some outdoor models include a cooling piston in

the accessory bag.)
Heating piston is shipped in the service valve 

 refer to

section F.
Example fan coils with piston: FEM4P, FSM4P, FSU4P,

FMA4P, FMC4P, FMU4P, WAPM, WAPT, WAPL, WAMA,

WAMC.
See Figure 2.
When changing indoor piston, use a back

up wrench.

Finger tighten hex nut, then tighten with wrench 1/2 turn.

Do not exceed 30 ft

lbs (40.7 N

m).The indoor piston

contains a Teflon ring (or seal) which is used to seat

against the inside of distributor body, and must be

installed properly to ensure proper seating in the direction

for cooling operation.

Figure 2

Indoor (cooling) Piston

TEFLON SEAL

BRASS

HEX NUT

STRAINER

PISTON
RETAINER

BRASS
HEX BODY

DISTRIBUTOR

PISTON

FLOW IN
COOLING

TEFLON RING

L10S017

!

CAUTION

PRODUCT OPERATION HAZARD

Failure to follow this caution may result in improper product
operation.
If using a TXV in conjunction with a single

phase reciprocat-

ing compressor, a compressor start capacitor and relay are
required. Consult outdoor unit pre

sale literature for start as-

sist kit part number.

B. REFRIGERANT LINE SETS

The refrigerant line set must be properly sized to assure

maximum efficiency and proper oil circulation.

Refer to Product Specifications and Long Line

Applications Guideline for line set sizing

.

NOTE:

 Total line set length must not exceed 200 feet

(61m).

NOTE:

 A crankcase heater must be used when the

refrigerant line length exceeds 80 feet (24.4m).
If outdoor unit is more than 10 feet (3m) higher than the

indoor coil, refer to the Long Line Applications Guideline

for instructions.

NOTE:

 When the outdoor unit is higher than the indoor

coil, the vertical separation must not exceed 100 feet

(30m).

NOTE:

 When the outdoor unit is lower than the indoor

coil, the vertical separation must not exceed 50 feet

(15.2m).
If it is necessary to add refrigerant line in the field, use

dehydrated or dry, sealed, deoxidized, copper

refrigeration tubing. Do not use copper water pipe.
Do not remove rubber plugs or caps from copper tubing

until connections are ready to be made.
Be extra careful when bending refrigeration tubing.

Tubing can “kink” easily, and if this occurs, the entire

length of tubing must be replaced.

!

WARNING

PERSONAL INJURY HAZARD
Failure to relieve system pressure could result in

personal injury and/or death.
Relieve pressure and recover all refrigerant before

servicing existing equipment, and before final unit

disposal. Use all service ports and open all flow

control devices, including solenoid valves.

!

CAUTION

UNIT OPERATION HAZARD
Failure to follow this caution may result in improp-

er product operation.
Do not leave system open to atmosphere any lon-

ger than absolutely required for installation. Inter-

nal system components 

 especially refrigerant

oils 

 are extremely susceptible to moisture con-

tamination. Keep ends of tubing sealed during

installation until the last possible moment.

C. ROUTING AND SUSPENDING REFRIGERANT

LINES

Run refrigerant lines as straight and direct as possible,

avoiding unnecessary bends and turns. Always insulate

the entire suction line. Both lines should be insulated

when routed through an attic or when routed through an

underground raceway.

Summary of Contents for R4H3 Series

Page 1: ...e following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on p...

Page 2: ...r intakes vents or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the un...

Page 3: ...1 4 540 26x26 660x660 31 1 8x31 1 8 791x791 9 1 16 230 6 1 2 165 24 5 8 625 31 1 2x31 1 2 800x800 C FASTENING UNIT DOWN If conditions or local codes require the unit be attached in place remove the k...

Page 4: ...ine Applications Guideline for line set sizing NOTE Total line set length must not exceed 200 feet 61m NOTE A crankcase heater must be used when the refrigerant line length exceeds 80 feet 24 4m If ou...

Page 5: ...operation Do not bury more than 36 1m of line set under ground Refrigerant may migrate to cooler buried section during extended periods of unit shut down causing refrigerant slugging and possible com...

Page 6: ...efer to Figure 5 Replace valve core when brazing is completed WARNING FIRE HAZARD Failure to remove refrigerant and oil charge before brazing could result in personal injury death and or property dama...

Page 7: ...ur During this time dry nitrogen will diffuse throughout the system absorbing moisture 5 Repeat this procedure as indicated in Figure 7 6 After the final evacuate sequence confirm there are no leaks i...

Page 8: ...e panel or a properly driven and electrically grounded ground rod Wiring Connections Make all outdoor electrical supply Line Voltage connections with raintight conduit and fittings Most codes require...

Page 9: ...DOOR FAN COIL WHEN INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W 3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2...

Page 10: ...circuit and operation of the defrost thermostat itself will not be observed Skip to 3 2 Use a volt meter to confirm there is no voltage across the DFT leads 24 volts across the SFT terminals indicates...

Page 11: ...ithout notice Figure 12 Defrost Control Board R8 OF1 K1 O1 R21 C2 R6 H9C1 C US R14 R13 D13 R7 C4 C10 JW2 JW1 D3 C16 C7 R28 D6 JW3 C13 R4 R1 R2 R3 R11 R5 R26 D1 D2 D10 A29 R9 D4 C19 C9 C1 OF2 CEBD43052...

Page 12: ...range NOTE If line length is beyond 80 feet 24 4m or greater than 20 feet 6 1m vertical separation See Long Line Guideline for special charging requirements A UNITS WITH COOLING MODE TXV Units install...

Page 13: ...34 37 24 3 5 7 8 10 12 13 16 17 19 21 80 5 8 12 15 18 21 25 28 31 35 27 3 4 7 8 10 12 14 16 17 19 85 8 11 15 19 22 26 30 33 29 4 6 8 11 12 14 17 18 90 5 9 13 16 20 24 27 31 32 3 5 7 9 11 13 15 17 95 6...

Page 14: ...26 299 90 32 88 31 86 30 84 29 82 28 80 27 308 92 33 90 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88...

Page 15: ...3 FS M U 4P24 A TXV 5 3 ED 4X30 EA 4X30 14 17 A 3 EN 4X30 3 3 EHD4X30A 3 3 FEM4 P X 30 A TXV 3 FSA4X30 A 3 FEA4X30 A 3 FXM4X30 A 5 5 FS M U 4P30 A TXV 5 5 FVM FCM 4X36 5 3 ED 4X36 EA 4X36 14 17 21 A 5...

Page 16: ...cer bringing on the first bank supplemental electric heat and providing electrical potential to the second heater sequencer if used If outdoor temperature falls below the setting of the outdoor thermo...

Page 17: ...ith other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not i...

Reviews: