background image

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pump

6

428 01 5301 05

Specifications subject to change without notice.

will be lost. Leave the plugs in place until line set tubing is

ready to be inserted.
Heat pumps require a piston metering device in the liquid

service valve for proper heating operation. Piston is

shipped in the piston body of the liquid service valve,

temporarily held in place with a plastic cap. Do not remove

the plastic cap until line set tubing is ready to be installed.
Refer to Figure 5 and follow these steps for piston

installation:

1. Remove plastic cap holding piston in piston body of

liquid service valve.

2. Check that piston size (stamped on side of piston)

matches with number listed on unit rating plate.

Return piston to piston body of liquid service valve

(either direction).

3. Find plastic bag taped to unit containing copper

adapter tube, brass nut, and plastic washer.

4. Install plastic washer in the seat inside piston body.
5. Fit brass nut onto adapter tube and install tube

onto liquid service valve. Tighten nut finger tight,

then wrench additional 

½

 turn only 15

ft lbs. Over

tightening may damage the plastic washer.

Service valve bodies are brass and suction tube stub is

copper.

Figure 5

Liquid Service Valve with Heating

Piston and Adapter Tube

PISTON BODY

LIQUID SERVICE VALVE

PISTON

PLASTIC WASHER

ADAPTER TUBE

BRASS NUT

Vapor Service Valve

VALVE CORE

SERVICE VALVE

G. BRAZING CONNECTIONS

NOTE:

For Liquid Service Valve 

 Braze lineset to adapter tube

BEFORE bolting adapter to valve.  This helps prevent

overheating and damage to plastic washer or o

ring.

For Vapor Service Valve 

 remove valve core from

schrader port on Service Valve BEFORE brazing.  This

helps prevent overheating and damage to valve seals

(refer to Figure 5). Replace valve core when brazing is

completed.

!

WARNING

FIRE HAZARD
Failure to remove refrigerant and oil charge before

brazing could result in personal injury, death, and/

or property damage.
Refrigerant and oil mixture could ignite and burn

as it escapes and contacts brazing torch. Make

sure the refrigerant charge is properly removed

from both the high and low sides of the system be-

fore brazing any component or lines.

Clean line set tube ends with emery cloth or steel brush.

Remove any grit or debris.
Insert line set tube ends into service valve tube stubs.
Apply heat absorbing paste or heat sink product between

service valve and joint. Wrap service valves with a heat

sinking material such as a wet cloth.
Braze joints using a Sil

Fos or Phos

copper alloy.

!

CAUTION

PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product

damage.
Braze with Sil

Fos or Phos

copper alloy on cop-

per

to

copper joints and wrap a wet cloth around

rear of fitting to prevent damage to TXV.

H. EVACUATING LINE SET AND INDOOR COIL

The unit is shipped with a factory refrigerant charge. The

liquid line and suction line service valves have been

closed after final testing at the factory. Do not disturb

these valves until the line set and indoor coil have been

evacuated and leak checked, or the charge in the unit

may be lost.

NOTE:

 Do not use any portion of the factory charge for

purging or leak testing. The factory charge is for filling the

system only after a complete evacuation and leak check

has been performed.

!

CAUTION

PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product

damage.
Never use the outdoor unit compressor as a vacu-

um pump. Doing so may damage the compressor.

Line set and indoor coil should be evacuated using the

recommended deep vacuum method of 500 microns. If

deep vacuum equipment is not available, the alternate

triple evacuation method may be used by following the

specified procedure.

Summary of Contents for R4H3 Series

Page 1: ...e following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on p...

Page 2: ...r intakes vents or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the un...

Page 3: ...1 4 540 26x26 660x660 31 1 8x31 1 8 791x791 9 1 16 230 6 1 2 165 24 5 8 625 31 1 2x31 1 2 800x800 C FASTENING UNIT DOWN If conditions or local codes require the unit be attached in place remove the k...

Page 4: ...ine Applications Guideline for line set sizing NOTE Total line set length must not exceed 200 feet 61m NOTE A crankcase heater must be used when the refrigerant line length exceeds 80 feet 24 4m If ou...

Page 5: ...operation Do not bury more than 36 1m of line set under ground Refrigerant may migrate to cooler buried section during extended periods of unit shut down causing refrigerant slugging and possible com...

Page 6: ...efer to Figure 5 Replace valve core when brazing is completed WARNING FIRE HAZARD Failure to remove refrigerant and oil charge before brazing could result in personal injury death and or property dama...

Page 7: ...ur During this time dry nitrogen will diffuse throughout the system absorbing moisture 5 Repeat this procedure as indicated in Figure 7 6 After the final evacuate sequence confirm there are no leaks i...

Page 8: ...e panel or a properly driven and electrically grounded ground rod Wiring Connections Make all outdoor electrical supply Line Voltage connections with raintight conduit and fittings Most codes require...

Page 9: ...DOOR FAN COIL WHEN INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W 3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2...

Page 10: ...circuit and operation of the defrost thermostat itself will not be observed Skip to 3 2 Use a volt meter to confirm there is no voltage across the DFT leads 24 volts across the SFT terminals indicates...

Page 11: ...ithout notice Figure 12 Defrost Control Board R8 OF1 K1 O1 R21 C2 R6 H9C1 C US R14 R13 D13 R7 C4 C10 JW2 JW1 D3 C16 C7 R28 D6 JW3 C13 R4 R1 R2 R3 R11 R5 R26 D1 D2 D10 A29 R9 D4 C19 C9 C1 OF2 CEBD43052...

Page 12: ...range NOTE If line length is beyond 80 feet 24 4m or greater than 20 feet 6 1m vertical separation See Long Line Guideline for special charging requirements A UNITS WITH COOLING MODE TXV Units install...

Page 13: ...34 37 24 3 5 7 8 10 12 13 16 17 19 21 80 5 8 12 15 18 21 25 28 31 35 27 3 4 7 8 10 12 14 16 17 19 85 8 11 15 19 22 26 30 33 29 4 6 8 11 12 14 17 18 90 5 9 13 16 20 24 27 31 32 3 5 7 9 11 13 15 17 95 6...

Page 14: ...26 299 90 32 88 31 86 30 84 29 82 28 80 27 308 92 33 90 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88...

Page 15: ...3 FS M U 4P24 A TXV 5 3 ED 4X30 EA 4X30 14 17 A 3 EN 4X30 3 3 EHD4X30A 3 3 FEM4 P X 30 A TXV 3 FSA4X30 A 3 FEA4X30 A 3 FXM4X30 A 5 5 FS M U 4P30 A TXV 5 5 FVM FCM 4X36 5 3 ED 4X36 EA 4X36 14 17 21 A 5...

Page 16: ...cer bringing on the first bank supplemental electric heat and providing electrical potential to the second heater sequencer if used If outdoor temperature falls below the setting of the outdoor thermo...

Page 17: ...ith other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not i...

Reviews: