INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pump

8

428 01 5301 05

Specifications subject to change without notice.

ELECTRICAL WIRING

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in

personal injury or death.
Before installing, modifying or servicing system,

main electrical disconnect switch must be in the

OFF position. There may be more than 1

disconnect switch. Lock out and tag switch with a

suitable  warning label.

Supply voltage must be 208/230 volts (197 volt minimum

to 253 volts maximum) 60 Hz single phase.
Outdoor units are approved for use with copper

conductors only. Do not use aluminum wire.
Refer to unit rating plate for minimum circuit ampacity and

circuit protection requirements.

Grounding

Permanently ground unit in accordance with the National

Electrical Code and local codes or ordinances. Use a

copper conductor of the correct size from the grounding

lug in control box to a grounded connection in the service

panel or a properly driven and electrically grounded

ground rod.

Wiring Connections

Make all outdoor electrical supply (Line Voltage)

connections with raintight conduit and fittings. Most

codes require a disconnect switch outdoors within sight of

the unit. Consult local codes for special requirements.
Route electrical supply (Line Voltage) wiring through

knockout hole in bottom of Control Box. Connect wires to

Contactor and Ground Lug according to Wiring Diagram

on unit. Refer to Figure 9.
Route thermostat wiring through rubber grommet in

bottom of Control Box. Low voltage lead wires are

provided in the control box for connection to thermostat

wires (use wire nuts). Refer to Wiring Diagram on unit and

Figure 10 for low voltage wiring examples.

NOTE:

 Use No. 18 AWG (American Wire Gage)

color

coded, insulated (35 

°

C minimum) wire. If

thermostat is located more than 100 feet (30.5 m) from

unit as measured along the control voltage wires, use No.

16 AWG color

coded wires to avoid excessive voltage

drop.

Figure 9

Electrical Supply (Line Voltage)

Connections

DISCONNECT

PER NEC AND/OR

LOCAL CODES

CONTACTOR

GROUND

LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

11

23 or 13

L1

L2

Summary of Contents for R4H3 Series

Page 1: ...e following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on p...

Page 2: ...r intakes vents or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the un...

Page 3: ...1 4 540 26x26 660x660 31 1 8x31 1 8 791x791 9 1 16 230 6 1 2 165 24 5 8 625 31 1 2x31 1 2 800x800 C FASTENING UNIT DOWN If conditions or local codes require the unit be attached in place remove the k...

Page 4: ...ine Applications Guideline for line set sizing NOTE Total line set length must not exceed 200 feet 61m NOTE A crankcase heater must be used when the refrigerant line length exceeds 80 feet 24 4m If ou...

Page 5: ...operation Do not bury more than 36 1m of line set under ground Refrigerant may migrate to cooler buried section during extended periods of unit shut down causing refrigerant slugging and possible com...

Page 6: ...efer to Figure 5 Replace valve core when brazing is completed WARNING FIRE HAZARD Failure to remove refrigerant and oil charge before brazing could result in personal injury death and or property dama...

Page 7: ...ur During this time dry nitrogen will diffuse throughout the system absorbing moisture 5 Repeat this procedure as indicated in Figure 7 6 After the final evacuate sequence confirm there are no leaks i...

Page 8: ...e panel or a properly driven and electrically grounded ground rod Wiring Connections Make all outdoor electrical supply Line Voltage connections with raintight conduit and fittings Most codes require...

Page 9: ...DOOR FAN COIL WHEN INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W 3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2...

Page 10: ...circuit and operation of the defrost thermostat itself will not be observed Skip to 3 2 Use a volt meter to confirm there is no voltage across the DFT leads 24 volts across the SFT terminals indicates...

Page 11: ...ithout notice Figure 12 Defrost Control Board R8 OF1 K1 O1 R21 C2 R6 H9C1 C US R14 R13 D13 R7 C4 C10 JW2 JW1 D3 C16 C7 R28 D6 JW3 C13 R4 R1 R2 R3 R11 R5 R26 D1 D2 D10 A29 R9 D4 C19 C9 C1 OF2 CEBD43052...

Page 12: ...range NOTE If line length is beyond 80 feet 24 4m or greater than 20 feet 6 1m vertical separation See Long Line Guideline for special charging requirements A UNITS WITH COOLING MODE TXV Units install...

Page 13: ...34 37 24 3 5 7 8 10 12 13 16 17 19 21 80 5 8 12 15 18 21 25 28 31 35 27 3 4 7 8 10 12 14 16 17 19 85 8 11 15 19 22 26 30 33 29 4 6 8 11 12 14 17 18 90 5 9 13 16 20 24 27 31 32 3 5 7 9 11 13 15 17 95 6...

Page 14: ...26 299 90 32 88 31 86 30 84 29 82 28 80 27 308 92 33 90 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88...

Page 15: ...3 FS M U 4P24 A TXV 5 3 ED 4X30 EA 4X30 14 17 A 3 EN 4X30 3 3 EHD4X30A 3 3 FEM4 P X 30 A TXV 3 FSA4X30 A 3 FEA4X30 A 3 FXM4X30 A 5 5 FS M U 4P30 A TXV 5 5 FVM FCM 4X36 5 3 ED 4X36 EA 4X36 14 17 21 A 5...

Page 16: ...cer bringing on the first bank supplemental electric heat and providing electrical potential to the second heater sequencer if used If outdoor temperature falls below the setting of the outdoor thermo...

Page 17: ...ith other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not i...

Reviews: