39
8.
Also record the combustion analysis details from
the combustion analyser and record the details
on the commissioning sheet.
9.
When the „Burner display reads „WAIT PELLET
THERMOSTAT‟, remove the burner burn-back
thermistor from the pellet feed tube. The Burner
display should read
„SAFETY CHARGE PIPE
THERMOSTAT
‟ once the burn-back thermistor
is disconnected. Refit the thermistor then press
reset the burner will be operational.
Fig. 9.11
10.
When the boiler is in „WAIT BOILER
THERMOSTAT
‟ mode check the burner door
interlock is operating by opening the combustion
chamber door. The burner led display should
then be switched off, closing the door should
power up the display. This confirms that the door
interlock is operating.
The interlock on the burner door disconnects the
power to the burner to prevent firing when
the door is opened. It does not extinguish the
flame immediately. If the burner door is
opened during the operation of the burner
there can be a large uncontrollable flame
emitted from the brazier.
11. Check the condition of the pellet delivery hose
and ensure it forms an air tight seal each end.
Check for damage and replace if necessary. A
damaged pellet delivery hose can allow a back
draft through the boiler resulting in burner
displaying error
„SAFETY CHARGE PIPE
THERMOSTAT‟.
12. If a condensate pump is fitted, check that a
condensate holding tank of at least 40 litres is
also fitted. This is to ensure that when the boiler
cleaning cycle has operated the holding tank can
collect the total volume of the water used in the
wash down and the condensate pump can then
discharge the waste effectively. Also check that
the burner settings
„T18‟ (TIME-BOILER
CLEANING OPERATION) is not set greater than
600 (60 seconds) and that
„T17‟ (TIME (MIN)
BETWEEN CLEANINGS) is not set less than
240 minutes, as modifying these times could
result in larger and more frequent wash down of
the boiler which could exceed the capabilities of
the tank and condensate pump.
WARNING
!
Summary of Contents for Spira 6-26kW
Page 3: ...3 Grant SPIRA Condensing Wood Pellet Boiler Intermediate Hopper ...
Page 26: ...26 NO 1 NO 2 NO 3 GRANT WOOD PELLET 6 26 9 36 BURNER WIRING DIAGRAM FIGURE 7 4 ...
Page 53: ...53 12 Spare parts 12 1 Burner Burner controls Exploded view Fig 12 1 ...
Page 54: ...54 Burner Brazier Exploded view Fig 12 2 ...
Page 56: ...56 12 2 Boiler Exploded view Fig 12 3 SPIRA 6 26 boiler displayed Boiler parts list ...