Note 1.
Before the „PRE-LOAD‟ operation commences and during the LIGHTING FEED REDUCED period, the
burner controls check that burner fan has enough air pressure generated to close the air pressure switch. If during
these operations the pressure switch is not closed then the warn
ing „AIR PRESSURE ERROR‟ is displayed on the
burner screen.
Note 2. During the
‟PELLET BURNER FIRING‟ operation the burner controls checks that the burner fan speed is
correct. (It does not check if the fan is generating enough air pressure). If during the
‟PELLET BURNER FIRING‟
operation
the burner fan speed is not correct then the warning „AIR PRESSURE ERROR‟ is displayed on the burner
screen.
Note 3. Check the condition of the air supply tube to the pressure switch, replace if necessary.
Note 4. Using a digital manometer (set for positive pressure) connected as shown below. Check the burner fan is
generating a minimum air pressure of 0.8mbar to activate the air pressure switch.
FIRE BOILER,
CHECK FOR
FAULT DURING
LIGHTING
SEQUENCE
NO
YES
RESET ERROR
MESSAGE BY
PRESSING
'RESET' ON
BURNER DISPLAY
1
2
3
6
5
4
!
SET
RESET
SET 60°C
H2o 60°C
AIR PRESS
Error symbol
AIR PRESSURE ERROR
= PRIMARY FAULT
= SECONDARY FOLLOW ON CHECKS
YES
CHECK BURNER
FAN IS
OPERATIONAL &
NOT BLOCKED
YES
CHECK PRESSURE
SWITCH
OPERATION &
CONDITION OF AIR
SUPPLY TUBE
CHECK BURNER
FAN IS
OPERATIONAL &
NOT BLOCKED
NO
CLEAR
BLOCKAGE
AND/OR REPLACE
FAN
NO
CHECK BURNER
FAN PRESSURE IS
CORRECT
NO
REPLACE
BURNER FAN
-CORRECT FAN
PRESSURE
ACHIEVED
NO
REPLACE MAIN
BURNER PCB
note 1
note 3
note 2
note 4
Summary of Contents for Spira 6-26kW
Page 3: ...3 Grant SPIRA Condensing Wood Pellet Boiler Intermediate Hopper ...
Page 26: ...26 NO 1 NO 2 NO 3 GRANT WOOD PELLET 6 26 9 36 BURNER WIRING DIAGRAM FIGURE 7 4 ...
Page 53: ...53 12 Spare parts 12 1 Burner Burner controls Exploded view Fig 12 1 ...
Page 54: ...54 Burner Brazier Exploded view Fig 12 2 ...
Page 56: ...56 12 2 Boiler Exploded view Fig 12 3 SPIRA 6 26 boiler displayed Boiler parts list ...