128
Zodiak Installation and Service Manual
Section 3 — Configuration
If the Calculation Method is Bus Selection, and if the Level is M/E 1, M/E
2, M/E 3, or Pgm-Pst, and the user touches a Tributary data box, the fol-
lowing popup in
appears. All the input buses in the M/E are
shown, and the key buses are shown as separate Fill (video) and Cut (key)
buses.
Figure 88. Tally Bus Popup Menu
Tally Relays
There is one group of 32 Tally relays. The group can be associated with any
combination of the five tally calculations, and each relay in the group can
be associated with a different source. For example, the relays could be con-
figured for On Air tally with the first relay tallying source 14, the second tal-
lying source 47, etc.
Combining tally calculations when configuring tally relay groups can often
minimize external wiring and conserve relays. For example, if an aux bus
feeds the record input to a replay device, a user tally calculation can be set
up for output tally of that aux bus and combined with the On Air tally cal-
culation. This permits Auto Start, etc. to function normally, but the On Air
relay closures will include the source feeding the replay recorder.