DC Inverter U-match Series Duct Type Unit
33
Clamp(attachment)
Drain lift pipe
1000mm~1500mm
Hoisting stand
≤1000mm
300mm
Drain hose
Roof
The vertical height of the drain hose should be 75mm or less so
that it is unnecessary for the drain port to withstand additional force.
Drain hose
≤75mm
≤1000mm
When multiple drain hoses are used, their installation should be
performed as shown in the figure below.
Notice:
The specification of the selected merged drainage
pipe shall be appropriate for the operation capacity of the unit.
(4) Drain branch should be connected to the vertical or horizontal
part of the main drain pipe.
(5) Horizontal pipe should not be connected to the vertical pipe
that is on the same level. It should be connected in the