23
Energy-Recovery Ventilation
System Service Manual
MAINTENANCE
1 TROUBLE TABLE
Error
Error code
Logic
Communication error
E6
Communication between the main board and the wire remote
controller is in trouble.
Indoor temp sensor error
F0
Something is wrong with temp sensor or the temperature is
overstep the range of the temp sensor.
Humidity sensor error
L1
Humidity sensor is not connected or communication is in trouble.
Outdoor temp sensor error
F3
Something is wrong with temp sensor or the temperature is
overstep the range of the temp sensor.
Air valve and relevant fitting error
or wrong connection of centralized
control wiring of air valve
L0
By-pass door and drive structure of the unit loose.
After debugging and trial run, the unit can be normally used by the user. If any fault occurs, remove it firstly by yourself
according to the following table before you contact us.
No.
Phenomenon
Possible causes
Solutions
1
Airflow volume at air
outlet/inlet is obviously
decreased after a
period of time.
Too much dust gathers on
the air filter.
Re-fix the collecting place of air vent.
2
Noise occurs at air vent.
Installation of air
vent is loose.
Re-fix the collecting place of air vent.
3
The system can
not be started.
No power supply
or power cord is
incorrectly connected.
Terminals of main board
transformer are loose.
Communication fault (E6).
Air valve and
relative fittings
are faulted (L0).
The centralized controller
of air valve of main board
is not connected (L0).
Repair the power supply and check power
cord according.
Repair the power supply and check power
cord according to circuit diagram on the unit.
Re-insert and connect transformer terminals.
Check the connecting wire between
displayer and main board.
Check by-pass door and drive
structure of the unit and fix it.
Connect CONTROPL port of main board;
with live line or pinboard of air dampers.
4
There is not air from
indoor or outdoor vent
after opening the switch.
1. No power supply
or power cord is
incorrectly connected.
2. Control wire is not or
incorrectly connected.
1. Check power and power supply
2. Check the connecting line between
operational box and main unit.
Summary of Contents for EH01100030
Page 1: ...Energy Recovery Ventilation System Service Manual GC201202 I ...
Page 3: ...1 Energy Recovery Ventilation System Service Manual PRODUCT PRODUCT ...
Page 8: ...6 Energy Recovery Ventilation System Service Manual CONTROL CONTROL ...
Page 9: ...7 Energy Recovery Ventilation System Service Manual CONTROL CONTROL 1 OPERATION FLOWCHART ...
Page 18: ...16 Energy Recovery Ventilation System Service Manual INSTALLATION ...
Page 24: ...22 Energy Recovery Ventilation System Service Manual MAINTENANCE ...
Page 26: ...24 Energy Recovery Ventilation System Service Manual 2 FLOW CHART OF TROUBLE SHOOTING ...
Page 28: ...26 Energy Recovery Ventilation System Service Manual 3 Model FHBQ D15 D FHBQ D20 D ...
Page 34: ...32 Energy Recovery Ventilation System Service Manual 2 Exploded view for model FHBQ D30 M D ...
Page 36: ...JF00300198 global cn gree com ...