26
Energy-Recovery Ventilation
System Service Manual
3 WIRING DIADRAM
([WHUQDOZLULQJ¿JXUHRIWKHXQLW,IWKLVRQHLVGLIIHUHQWIURPZLULQJ¿JXUHRIMXQFWLRQER[WDNHWKHZLULQJER[
of junction box as standard) .
1) Model:FHBQ-D3.5-K;FHBQ-D5-K;FHBQ-D8-K;FHBQ-D10-K.
Note:
1.When need humidifier,connect "1" and "2" terminal (220V
̚ˈ
1A) to the contactor
coil of the humidifier.Meanwhile,connect the humidification sensor to HUMIDITY terminal
on the main board.
2.Wire the CN9 on the main board to the united control to access a center control to the air
valves.
3.The part with broken line is optional for user.
Remote
Control
Wired
controller
POWER
PE
L
N
Humidity sensor
United control
Humidifier
AC Contactor Coil
2) Model:FHBQ-D15-M;FHBQ-D20-M.
Humidity sensor
United control
Note:
1.When need humidifier,connect "1" and "2" terminal (220V
̚ˈ
1A) to the contactor
coil of the humidifier.Meanwhile,connect the humidification sensor to HUMIDITY terminal
on the main board.
2.Wire the CN9 on the main board to the united control to access a center control to the air
valves.
3.The part with broken line is optional for user.
Remote
Control
Wired
controller
POWER
PE
L1
L2
L3
N
Humidifier
AC Contactor Coil
Summary of Contents for FHBQ-D10-K
Page 3: ...1 Energy Recovery Ventilation System Service Manual PRODUCT QSPEVDU ...
Page 8: ...6 Energy Recovery Ventilation System Service Manual CONTROL DPOUSPM ...
Page 19: ...17 Energy Recovery Ventilation System Service Manual INSTALLATION ...
Page 25: ...23 Energy Recovery Ventilation System Service Manual MAINTENANCE ...
Page 38: ...36 Energy Recovery Ventilation System Service Manual Model FHBQ D30 M Exploded View ...