Product Introduction
Basic Functions - 18K & 24K 230 volt
2. When the thermo-bulb is detected in open circuit continuously for 30 seconds: stop the machine in protection,
directly display corresponding faults of the thermo-bulb.
3. Forced Running Function of the Indoor Units
(1) Enter into Forced Running Control Within 5 minutes after power-up, press the Lights Off button on the remote
controller continuously for three times within 3 seconds to enter into the fluorine collecting mode, and display Fo,
send the fluorine-collecting mode for 25 minutes continuously, each load will be treated as cooling when starting the
machine (set the air flow as High, set the temperature as 60.8 °F).
(2) Exit from the Forced Running Control After receiving any remote signal, or signal of keys, the fluorine-collecting
mode will exit, and operate in accordance with the current orders set; or exit the fluorine-collecting mode after
running for 25 minutes, and the machine will be shut down automatically.