78
Test Operation, Troubleshooting and Maintenance
4.4.2 Replacement instructions
(1) LSQWRF35VM/NaA-M and LSQWRF35VM/NhA-M
Replacement of the compressor
Note: be sure there is no refrigerant inside the system and power supply has been cut off before
replacement.
Steps
Image
Instructions
1. Remove the
front panels.
• Remove screws at the front
pane.
• Loosened screws should be
put together to avoid loss.
• Pull the front panel upwards
and then remove it.
•
Properly keep the removed
front panel to avoid from
being damaged.
• Note: there are two clasps
at each panel for connecting
with side panels.
2. Remove power
lines and the
electric heater.
•
Remove the insulation of the
compressor.
• Loosen screws of power lines
with a screwdriver.
• Draw out power lines.
• Draw out the electric heater.
• Note: power lines and
their terminals should be
numbered to avoid incorrect
rewiring.
3. Disconnect
power lines to the
compressor.
•
Desolder pipes quick to avoid
deformation.
•
Keep the replaced
compressor complete for
further analysis.
Summary of Contents for LSQWRF35VM/NaA-M
Page 5: ...1 Product Product...
Page 18: ...14 Unit Control Unit Control...
Page 29: ...25 Unit Installation Unit Installation...
Page 58: ...54 Unit Installation 3 5 7 Electric wiring digram 1 LSQWRF35VM NaA M...
Page 59: ...55 Unit Installation 2 LSQWRF60VM NaA M LSQWRF65VM NaA M...
Page 60: ...56 Unit Installation 3 LSQWRF35VM NhA M...
Page 61: ...57 Unit Installation 4 LSQWRF60VM NhA M...
Page 62: ...58 Unit Installation 5 LSQWRF130VM NhA M...
Page 63: ...59 Unit Installation...
Page 64: ...60 Unit Installation The electric wiring diagrams on the unit always prevail...