33
Unit Installation
3.3.2 Precautions for installation
(1) Pipelines and electric lines should be correctly connected.
(2) Rubber pads and rubber flexible connectors should be used during installation for noise and
vibration reduction.
(3)
Under subzero climate, when the heat pump runs for cooling, anti-freeze liquid is required.
(4) Dedicated lugs should be used for lifting. During lifting, proper protection should be taken so as to
avoid pipelines from being damaged.
3.3.3 Installation environment
(1)
The unit should not be installed within 25m of the residence; otherwise a sound insulating wall
should be set up.
(2) When the unit is to be installed at the roof, the foundation should be located at the heel posts. If the
floor is quite thin, or there is vip rooms under the floor, the spring damper is required.
(3)
Fire, inflammably, corrosive gas and waste gas should be avoided around the unit. Also, the unit
cannot be installed around the chimney and discharge fan.
(4)
Ventilation should be in good condition and no air flow would be trapped.
3.3.4 Installation and service space
The interval between each single unit should be larger than 0.5m so that there is enough space for
entering air and maintenance. The distance between the unit and any barrier should be or larger than 1m
so as to keep good ventilation around the unit.
If possible, a suncover can be set up 3m ahead of the unit.
Outlet
Outlet
Outlet
Outlet
Inlet
Inlet
Electric box
The inlet and outlet pipes
both are at this side.
Electric box
The inlet and outlet pipes
both are at this side.
Inlet
Inlet
Inlet
Inlet
Inlet
Inlet
Inlet
Inlet
Inlet
Inlet
Inlet
Summary of Contents for LSQWRF35VM/NaA-M
Page 5: ...1 Product Product...
Page 18: ...14 Unit Control Unit Control...
Page 29: ...25 Unit Installation Unit Installation...
Page 58: ...54 Unit Installation 3 5 7 Electric wiring digram 1 LSQWRF35VM NaA M...
Page 59: ...55 Unit Installation 2 LSQWRF60VM NaA M LSQWRF65VM NaA M...
Page 60: ...56 Unit Installation 3 LSQWRF35VM NhA M...
Page 61: ...57 Unit Installation 4 LSQWRF60VM NhA M...
Page 62: ...58 Unit Installation 5 LSQWRF130VM NhA M...
Page 63: ...59 Unit Installation...
Page 64: ...60 Unit Installation The electric wiring diagrams on the unit always prevail...