35
Unit Installation
3.3.7 Placement of the main unit
(1) Place the unit on the foundation.
(2)
There should be no clearance between the foundation and the baseboard of the unit.
(3) Lift the unit, put the rubber pad on the foundation and then place the unit on the rubber pad. After
that, be sure the horizontal slope of the unit can’t exceed 1/1000. If so, take an adjustment by
stuffing spacers into the clearance between the foundation and the baseboard of the unit until the
slope is satisfactory.
Vibration isolator
Installation foundation
Drain
3.4 Piping and insulation
3.4.1 Installation of the water system
Considerations stated below shall be taken for the water system.
(1)
Each water inlet and outlet should be labeled properly to avoid misconnection.
(2)
A flexible connector should be used at the chilled water outlet to reduce vibration transmission.
(3)
A manometer, a thermometer and a gate valve shall be installed at the chilled water inlet /outlet.
Moreover, a drain valve shall be installed at the outlet and an air release valve shall be installed at
the inlet. At the highest point of the water system, another release valve shall be installed, while at
the lowest point of the water system, another drain valve shall be installed to facilitate drainage.
(4)
The water inlet/outlet pipe should be tightly insulated to reduce heat loss and dewing. When pipes
are exposed under 0°C, a electric heater shall be installed.
(5)
A filter shall be installed upstream of the water pump, otherwise there will be foreign matter entering
the water system, then generating scale on the surface of heat exchangers.
(6)
Construct a temporary bypass around the unit to prevent drainage from flowing back to the interior
of the unit.
(7)
Under ultra-low temperature in winter, showdown at night will cause the evaporator and pipeline
frozen up, so it is highly recommended to add alcohol and propanol mixture in chilled water. Do not
cut off the power supply when the unit is turned off, otherwise the freeze protection does not work.
Alternatively, cut off the power supply and drain the water system thoroughly.
Summary of Contents for LSQWRF35VM/NaA-M
Page 5: ...1 Product Product...
Page 18: ...14 Unit Control Unit Control...
Page 29: ...25 Unit Installation Unit Installation...
Page 58: ...54 Unit Installation 3 5 7 Electric wiring digram 1 LSQWRF35VM NaA M...
Page 59: ...55 Unit Installation 2 LSQWRF60VM NaA M LSQWRF65VM NaA M...
Page 60: ...56 Unit Installation 3 LSQWRF35VM NhA M...
Page 61: ...57 Unit Installation 4 LSQWRF60VM NhA M...
Page 62: ...58 Unit Installation 5 LSQWRF130VM NhA M...
Page 63: ...59 Unit Installation...
Page 64: ...60 Unit Installation The electric wiring diagrams on the unit always prevail...