VRF Protocol Gateway
9
Fig. 6.2 Communication method of BACnet and communication method network
topology of Modbus TCP
Internet topological graph statement:
485 bus
: L1 shown in Fig. 6.1 is 485 bus, one 485 bus can connect to 254
gateways at most.
Network table
: L1 shown in Fig. 6.2 is general network cable, the gateway can
connect to BMS via the network cable.
CAN1 network
: L3 shown in Fig. 6.2 is CAN1 bus, which consists of network
and all the outdoor units and indoor units of system; one CAN1 network can connect
to 80 sets of indoor units at most.
CAN2 network
: L2 shown in Fig. 6.2 is CAN2 bus, which consists of gateway
and master outdoor unit of system; one CAN2 network can connect to 16 sets of
outdoor units and 255 sets of indoor units. When the quantity of outdoor units
exceeds 16 or the quantity of indoor units exceeds 255, it should be divided into two
CAN2 networks.