VRF Protocol Gateway
10
System
: One system consists of one set of outdoor unit (one set of outdoor unit
is a module set, which can consist of 1~4 modules, that is, 1~4 sets of outdoor units)
and its indoor unit.
Connectable quantity of units of gateway: One gateway can connect to 16 sets
of outdoor units and 255 sets of indoor units at most.
Remarks
:
(1) One 485 bus can connect to 254 gateways at most, if there a re other 485
equipment in the 485 bus, the connectable gateway should reduce accordingly.
(2) It is recommended that the connecting quantity of gateway of 485 bus n is
less or equal to 16.
7 Product Installation
7.1 Product Size and Spatial Size for Electric Control Cabinet
Installation
7.1.1 Product Size
Fig. 7.1 Gateway product size chart
Notice for installation and operation:
(
1
)
Ensure the specification of power input. Otherwise, Gateway can’t work
normally or even be damaged.
(
2
)
Ensure the dial code setting of Gateway is correct. Otherwise, there will
be communication malfunction.