BACnet Gateway Kit for Central Air Conditioners
20
1.7 Description of a device type: PICS
PICS protocol implementation conformance statement All devices conforming to the BACnet
protocol shall have a Protocol Implementation Conformance Statement (PICS) that identifies all of
the portions of BACnet that are implemented.
A PICS is a written document, created by the manufacturer of a device, that identifies the
particular options specified by BACnet that are implemented in the device. A BACnet PICS is
considered a public document that is available for use by any interested party.
2 BACnet protocol implementation conformance statement(PICS)
Date: 08.08.2011
Vendor Name: Saia-Burgess Controls AG (Vendor ID = 89)
Product Names: BACnet_GMV1_V1.0
stations: PCD3.M6340
Product Model Number: PCD7.R560
Applications Software Version: -
Firmware Revision: BACnetPCD3Mxxx0_PCD2M5xx0_1.08.49.blk
BACnet Protocol Revision: 1.4
2.1 Product Description:
The BACnet gateway applied for GREE GMV units links the unit’s internal network
with
the BACnet/IP network
, and also provides BACnet BAS interfaces which enable the unit to be
seamlessly integrated into the third party’s BAS.
2.2 BACnet Standardized Device Profile (Appendix L):
□ BACnet Operator Workstation (B-OWS)
□ BACnet Building Controller (B-BC)
□ BACnet Advanced Application Controller (B-AAC)
■ BACnet Application Specific Controller (B-ASC)
□ BACnet Smart Sensor (B-SS)
□ BACnet Smart Actuator (B-SA)
2.3 List all BACnet Interoperability Building Blocks Supported (Appendix K):
1) Data Sharing BIBBs
Data Sharing Read-Property-B DS-RP-B
Data Sharing Read-Property-Multiple-B DS-RPM-B
Data Sharing Write-Property-B DS-WP-B
Data Sharing Write-Property-Multiple-B DS-WPM-B
Data Sharing COV-B DS-COV-B
Data Sharing COV-Unsolicited-B DS-COVU-B
Data Sharing COV-Property-B DS-COVP-B
2) Device Management BIBBs
Device Management-Dynamic Device Binding-A DM-DDB-A
Device Management-Dynamic Device Binding-B DM-DDB-B
Device Management-Dynamic Object Binding-B DM-DOB-B