BACnet Gateway Kit for Central Air Conditioners
38
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the error code of the GMV water heart. For more
details see Appendix E�
Present_Value:
0x00010000-0x0001FFFF (See Appendix E)
Note :
1) When some error occurs to the GMV water heater, Present_Value property will be a decimal
numeral related to the error code.
2) Multi errors may concur. Each error has a independent error code, e.g. 0x00000040 for “Water
Tank Upper Temp Sensor Error”, 0x00000080 for “Water Tank Lower Temp Sensor Error”. When
these two errors just happen together, Present_Value property will be192 (conversion method:
0x00000040 OR 0x00000080 is 0x000000C0,equal to192).
3) This parameter is only for the GMV water heater.
(19) Water tank temp(status)
Member number :18
Object name:WaterTankTempStatus_XX_YYY_ZZ (XX means Air condition type, like GMV
is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now;ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Analog Input
Object ID: AI(0)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the water tank temperature status of the GMV water
heater..
Present_Value:
① .
Hot Water, Night, Reserve modes:35
~58
(the upper limit can be adjusted to 65 );
② .
Energy saving mode:35
~50
;
③ .
High temp sterilization mode:65
~70
;
Units: degrees-Celsius or
Resolution: 1
Note :
1) The temperature status of the water tank varies as the change of the running mode of the
water tank.
2) This parameter is only for the GMV water heater.
(20) Water tank temp(setting)
Member number :19
Object name:WaterTankTempCommand_XX_YYY_ZZ (XX means Air condition type, like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type:Analog Value
Object ID: AV(2)+YYY*8192+ZZ*64+1