BACnet Gateway Kit for Central Air Conditioners
41
(25) Water tank mode(setting)
Member number :24
Object name:WaterTankModeCommand_XX_YYY_ZZ (XX means Air condition type, like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type:Multistate Value
Object ID: MV(19)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the mode setting of the water tank of GMV water
heater.
Present_Value:
1-energy saving mode mode;
2-reservation mode mode;
3-night mode;
4-hot water mode.
Note :
1) Present_Value can reflect the running mode of the water tank. That is, it varies as the
change of the water tank mode setting of the wired controller or the wires controller.
2) This parameter is only for the GMV water heater.
(26) Double-Tube supply Water Temp
Member number :25
Object name:DoubleTubeSupplyWaterTemp_XX_YYY_ZZ (XX means Air condition type, like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type: Analog Input
Object ID: AI(0)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the double-tube supply water temperature of GMV
water heater.
Present_Value:
-127-255
Units: degrees-Celsius or
Min_Pres_Value: -127
Max_Pres_Value: 255
Resolution:1
Note :
1) This parameter is only for the GMV water heater.
(27) Floor Heating supply water setting temp.
Member number :26
Object name:FloorHeatingSupplyWaterSettingTemp_XX_YYY_ZZ (XX means Air condition