BACnet Gateway Kit for Central Air Conditioners
42
type, like GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now;
ZZ means Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device
YYY's Parameters.)
Object type: Analog Value
Object ID: AV(2)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the setting temperature of floor heating of GMV water
heater.
Present_Value:
30-52
Units: degrees-Celsius or
Note :
1) This parameter is only for the GMV water heater with floor heating device.
(28) Disinfecting
Member number :27
Object name:Disinfecting_XX_YYY_ZZ (XX means Air condition type,like GMV is 01;YYY
means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means Indoor Unit's
number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's Parameters.)
Object type: Binary Input
Object ID: BI(3)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the disinfecting status of GMV water heater.
Present_Value:
ACTIVE: Yes
INACTIVE:No
Note:
1) This parameter is only for the GMV water heater.
(29) Floor heat power
Member number :28
Object name:FloorHeatPower_XX_YYY_ZZ (XX means Air condition type, like GMV is 01;YYY
means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means Indoor Unit's
number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's Parameters.)
Object type: Binary Input
Object ID: BI(3)+YYY*8192+ZZ*64+3
Instance Number: YYY*8192+ZZ*64+3
Description: this object is used to monitor the on/off status of the floor heating device of GMV
water heater.
Present_Value:
ACTIVE: On
INACTIVE:Off
Note :
1) This parameter is only for the GMV water heater.