MINI CHILLER PRODUCT
7
4.2 Operation Range
Mode
Range of Outdoor Temperature ( )
℃ ℃
Cooling 16~48
Heating -15~28
4.3 Pressure-loss Conversion Chart
Water Flow
(
m3/h
)
1.2 1.4 1.7
1.9 2.0
The percentage
(
%
)
70 80 100 110 120
Loss of Pressure (kPa)
200
100
0
100 200
NOTE:
The percentage is contrasted to nominal water flow.
4.4 Electrical Data
4.4.1 Split Type
Fan Motor
Compressor
Outdoor
Pump Total
Model
Rated
Power
Supply
NO
.
LRA
each
(
A
)
MR
C
each
(
A
)
NO.
MRC
(
A
)
MRC
(
A
)
MRC
(
A
)
NRC
(
A
)
HLR8WSZ-K
1 97 21.2
1 1.5 0.7 23.4 17
HLR10WSZ-K
2 49 13.2
2 2 0.7 31 22
HLR12.5WSZ-K
2 52 16.1
2 3 0.7 39 28
HLR15WSZ-K
220~240V
1Ph 50Hz
2 69 17 2 3 0.7 47 33.5
4.4.2 Integral Type
Compressor Fan
Motor
Pump
Total
Model
Rated
Power
Supply
NO.
LRA
each
(
A
)
MRC
each
(
A
)
NO.
MRC
(
A
)
MRC
(
A
)
MRC
(
A
)
NRC
(
A
)
HLR19S/A-M
2 42 9.5 2 5
1.5
19.5
14
HLR25S/A-M
2 56 11.2 2 5
1.5
23.5
16.8
HLR32S/A-M
2 69 13.4 2
7.5
3 39 28
HLR35S/A-M
2 101 15.3 2 7.5 3 42 30
HLR45S/A-M
380
~
415V
3Ph 50Hz
2 110 21.4 2 7.5 3 54
38.5
Notes:
LRA: Locked rotor amps (A)
MRC: Maximum running current (A)
NRC: Nominal running current (A)
Summary of Contents for T1/R22
Page 1: ...Mini Chiller Service Manual T1 R22 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Page 10: ...GREE COMMERCIAL AIR CONDITIONERS MINI CHILLER 9 CONTROL...
Page 11: ...MINI CHILLER CONTROL 10 UNITS CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Operation...
Page 21: ...GREE COMMERCIAL AIR CONDITIONERS MINI CHILLER 20 INSTALLATION...
Page 30: ...GREE COMMERCIAL AIR CONDITIONERS MINI CHILLER 29 MAINTENANCE...