33
System Operation 18,000/24,000 btuh Models, cont.
5)Auto Mode
Auto Mode Process
Setting the auto mode will run the unit in heat or cool automatically depending on T
indoor
ambient
1)Operating Parameters
A. If the T
indoor
ambient >= 790 F the unit will operate in cooling mode. The set temperature is 770 F.
B. If the T
indoor
ambient <= 720 F the unit will operate in heat mode. The set temperature is 680 F.
C. When the T
indoor
ambient <= 730 F and >= 770 F, the unit will operate in the previous state. If it is energized
for the first time, it will run in Fan mode
D. In auto mode, the cooling frequency will be the same as the cooling only mode and the heating frequency will
be the same as the heating only mode.
2) Protection
A. In cooling operation, protection is the same as the cooling only mode
B. In heating operation, protection is the same as the heating only mode
C. When the indoor ambient temperature changes, the operation mode will be automatically selected. Once started
the compressor will have a 6 minute run time.
Basic Functions
Product Introduction
Summary of Contents for TERRA09HP230V1A
Page 13: ...13 Product Introduction Operation Characteristic Curve ...
Page 14: ...14 Product Introduction Capacity Variation Ratio According to Temperature ...
Page 16: ...16 Noise Criteria Curve Tables Product Introduction ...
Page 54: ...54 Electrical Schematics ...
Page 135: ...135 Gree Electric Appliances Inc C 2014 Cat No DFS TERRA HP 2SM Version 2 0 ...