Gree VRF Protocol Gateway
15
2) Adopt parallel network cable, Gateway shall go through router to connect to PC.
(
2
)
Communication line connection between Gateway and AC units:
When gateway is connected to main control unit of ODU, ODU with the address dial-up of 0
must be connected.
CAN
G1
G2
D1D2 G1G2
1 2
ON ON
Main control
Unit of ODU
……
Subordinate
Unit of ODU
5.4 Gateway configuration:
One gateway connects to 16 sets of systems and 255 sets of indoor units simultaneously.
After installation, the parameters of gateway should be set. Before setting the parameters of
gateway, please set the IP address of PC as the same with the IP address in the same network
segment of gateway, as refer to appendix A; and then open the browser (IE10 and above version,
Firefox or Google), input the default IP address of gateway: http://192.168.1.150, default user
name: config, password: config; as shown below.
Setting of gateway protocol functions:
After inputting user name and password, click the arrow to enter the setting interface, as
shown in Fig. 7.12, 7.13, and 7.14; in the setting interface 1, you can select the protocol function;
in the setting interface 2, you can set the IP parameters of gateway; in the setting interface 3, you
can set the equipment information.
Note: When the gateway is energized, it will conduct default Modbus protocol function, when select to
reset the gateway and log on the gateway setting interface again, the protocol option of interface 1 is
blank, you can select according to demand.
Summary of Contents for VRF
Page 1: ...VRF Protocol Gateway ...
Page 18: ...Gree VRF Protocol Gateway 16 ...
Page 31: ...JF00304482 ...