Gree VRF Protocol Gateway
17
The settable parameters: IP address of gateway (in which setting of IP address: master unit
number should not be 0, all 0 refers to the whole network, such as 192.168.1.0; master unit
number should not be all 1, all 1 refers to broadcast address, such as 192.168.1.255; it is not
recommended to set the address by user, otherwise it may cause problems such as the network is
not accessible), subnet mask of gateway, default gateway, gateway name, gateway ID. User can
set by himself/herself according to the actual needs. After setting, click the arrow, the interface will
pop up a window to ask: Whether to restart the gateway to make the setting come into effect?
Click yes and then the gateway is restarted.
Chapter 2 Commissioning Operation
1 Commissioning of hardware
1.1 DIP Switch
NOTICE!
Before using this device, please conduct DIP switch setting first, otherwise the unit will not
function normally!
Gateway dial-up setting area is consisting of function DIP switch code.
(
1
)
Diagram of Dial-up Machine
(
2
)
The 1st Lever of Functional DIP Switch—CAN2 Bus Matched Resistance Setting
Main control ODU or gateway at the top/end of CAN2 bus must be with matched resistance;
otherwise the communication might be wrong!
※
CAN2 bus: Specific meaning shall refer to the specification in Fig Internet topological
graph.
The No.1 dial-up button in function dial-up machine shall be used in the setting in the matched
Summary of Contents for VRF