Gree VRF Protocol Gateway
23
Troubleshoo
ting 2
485-1 RX/TX indicator of gateway is
not flashing, no retrieval data
The gateway cannot receive the
data of BMS
Communication
cable
connection
between
gateway and
BMS is not
correct or the
communication
cable is not
conductive
Please check
if the form
and content
of data frame
sent by BMS
equipment to
gateway is
correct
Equipment
address of
gateway is
not correctly
set
Communica
tion
distance is
too long
Check the conductivity
of communication wire;
by referring to 2.1 of
Chapter 2, check if the
communication
connection between the
gateway and the air
conditioner is correct
By referring to 5.4 of
Chapter 2, check if there
is repeat equipment
address of gateway;
check if the equipment
address of command
frame sent by BMS
equipment is in consistent
with the address of
gateway
Add relay between the
gateway and BMS, or
reduce the
communication distance
to be within 800m