Chapter 3 Maintenance
1 Troubleshooting for common errors of BMS
Phenomenon
Possible Causes
Troubleshooting
According to the provided protocol, the
BMS displays communication error, some
or all the units cannot display under
operating status, and cannot control
The communication cable is not
twisted pair communication cable
Replace with twisted pair
communication cable
The gateway is damaged
Replace the gateway
The communication cable is
broken
Solder the disconnected cable
The communication cable is
short-circuited
Maintain the short-circuited part
The twisted pair is too close to
the power cord (less than 15cm),
the interference is to large and
cause communication error
Arrange the wires separately, if
they cannot be separate for
over 15cm, add shielding steel
tube
There is communication interface
connection error
Connect according to the
instruction of this guidline
The wires are checked to be normal, but
some or all of the units cannot display
information, there still be communication
error in the software
After the chip of outdoor unit is
replace or the dial code is reset,
the power supply has not been
disconnected and re-connected
Energize the unit
The matched resistance has not
been connected
Correctly set the matched
resistance
The serial ports used by
communication software is
inconsistent with the serial ports
of computer
Change the serial ports or alter
the serial port setting in the
software
The added unit address in the
software is inconsistent with the
actual address of unit
Alter the address setting of
software
The unit has not been energized
Energize the unit
The chip has not been installed
in the outdoor unit or indoor unit,
or the installing direction of chip
is reverse
Recheck and install the chip,
install according to the direction
of gap in the PCB, and then
re-energize the unit
The address of unit is wrong or
repeated
Alter the wrong address setting
The wires, equipment and engineering
installation are checked to be normal, but
there still be communication error in the
software
The display or controller cannot
match with the actual unit
Check the model of the
controller and remote controller
of the current unit, if it is not
matched, contact the customer
service center to replace
The wires are check to be normal, other
equipment layers are normal, only certain
equipment layer cannot display information
A relay should be added, or if the
relay has been installed, the wire
connection of relay may be
wrong
Install the relay correctly