Three-Phase UPS (10kVA-160kVA) Series
User Manual
2 Overview
29
2.7.4 Battery Cabinet/ Rack
The battery cabinet/ rack can be configured according to different backup time. For specific selection,
please consult our company.
2.7.5 Battery Switch Box
The battery switches in the battery switch box can configure DC breaker that can be wall-mounted in
the front or rear of battery rack. For specific selection, please consult our company. The switch
specification of corresponding model is as shown in Table2-3.
Table2-3
Configuration of the battery switch box
Power (kVA)
Switch capacity(A)
10
32
15
50
20
63
30
100
40
200
50
200
60
200
80
315
100
400
120
400
160
500
2.7.6 Top Waterproof Cover
The top waterproof cover meets the protection requirements of IP21. The protection grade of the UPS
is IP20, when the UPS is used where may be the risk of drip at vertical direction, please select the top
waterproof cover. As the height after equipped with the top waterproof cover is about 2300mm, the
vertical height should be more than 3000mm.