Three-Phase UPS (10kVA-160kVA) Series
User Manual
A Technical Specifications
97
Model
Index
Three-Phase (10kVA-160kVA) UPS
Wave form
Sine wave, THD<2% (Linear load)
Transfer time(ms)
<
1ms(Transfer from inverting mode to bypass mode)
0ms(Transfer from mains mode to battery mode)
O
ver
load
capac
ity
Inverting status
125% rated load: 10min later, turn to bypass.
150% rated load: 1min later, turn to bypass.
170% above rated load: turn to bypass immediately.
Bypass status
130% below rated load: Long time working
130%-170% rated load: 10min later, turn off bypass.
170%-200% rated load: 1min later, turn off bypass.
200% above rated load: turn off bypass immediately.
Output method
Copper bar
Envir
onm
ent
Operating temperature
-5
℃
~40
℃
Storage temperature
-20
℃
~+55
℃
(As the temperature of transportation and storage is -20
℃
, it is necessary to set
UPS alone for increasing temperature to 0
℃
and keep it for more than 4 hours
before starting UPS.)
Relative humidity
0%~95%(with no condensation)
Operating altitude
The operating altitude should be lower than 1000m. If exceeding 1000m, it need to
decrease the rated power according to GB/T 7260.3.
Noisy(dB)
<
65dB(A)
St
andar
d
EMC
IEC 62040-2 CLASS C3
Safety standard
IEC 60905-1
、
IEC 62040-1-1
、
UL1778
Design and test
IEC 62040-3