3 Installation
Three-Phase UPS (10kVA-160kVA) Series
User Manual
36
Input
Table3-1
Input current and cable specification of Three-Phase (10kVA-160kVA) series UPS
Power
(kVA)
Input
cur.
(A)
Live
wire
cross-sectiona
l area (mm
2
)/
terminal
Neutral wire
cross-sectiona
l area (mm
2
)/
terminal
Grounding
wire
cross-sectional
area
(mm
2
)/
terminal
Batt.
cur.(A)
Battery
wire(mm
2
)
/
terminal
10
31
6(RVS5.5-6)
6(RVS5.5-6)
6(RVS5.5-6)
26
6(RVS5.5-6)
15
41
10(RNBS8-6)
10(RNBS8-6)
10(RNBS8-6)
39
10(RNBS8-6)
20
52
10(RNBS8-6)
10(RNBS8-6)
10(RNBS8-6)
52
10(RNBS8-6)
30
74
16(RNBS14-6)
16(RNBS14-6)
16(RNBS14-6)
78
16(RNBS14-
6)
40
99
25(DT-25)
25(DT-25)
16(DT-16)
103
35(DT-35)
50
120
35(DT-35)
35(DT-35)
25(DT-25)
129
50(DT-50)
60
142
50(DT-50)
50(DT-50)
25(DT-25)
155
50(DT-50)
80
185
70(DT-70)
70(DT-70)
35(DT-35)
220
95(DT-95)
100
229
95(DT-95)
95(DT-95)
50(DT-50)
275
150(DT-150)
120
271
150(DT-150)
150(DT-150)
95(DT-95)
330
185(DT-185)
160
356
240(DT-240)
240(DT-240)
120(DT-120)
440
300(DT-300)
Output
Table3-2
Output current and cable specification of Three-Phase (10kVA-160kVA) series UPS
Power
(kVA)
Current (A)
Live
wire
cross-sectional
area
(mm
2
)/
terminal
Neutral
wire
cross-sectional
area
(mm
2
)/
terminal
Grounding wire
cross-sectional
area
(mm
2
)
/
terminal
10
15
2.5(RV2-6)
2.5(RV2-6)
2.5(RV2-6)