Hardware Override Switch Notes

ControlKeeper® TouchScreen Logic Board

Hardware Override Switch Notes

In addition to the individual relay override switches, there 

is a hardware override switch that allows the override of 

all relays on the board. All relays in the enclosure will be 

closed as long as the switch is in the ALL ON position. All 

relays in the enclosure will be open as long as the switch is 

in the ALL OFF position. The ON or OFF state is maintained 

regardless of programmed state. In order for relays to run 

programmed scheduling the hardware override switch must 

be in the AUTO or center position. See Figure 11 for location 

of the hardware override switch. 

Figure 11.  Enclosure Override Switch

LED Operation

The ControlKeeper T has LEDs located throughout the 

enclosure for system status monitoring. These will be 

discussed in three sections, including ControlKeeper T 

Status LEDs, RSC Status LEDs and Relay Card Status LEDs. 

ControlKeeper T Status LEDs

There are three (3) system status LEDs that are located 

in the upper left corner of the ControlKeeper T. There are 

two additional LEDs located in top middle of the board that 

diagnose digital switch communications. Please refer to 

Figure 12 for location of these status LEDs. These status 

LEDs will indicate proper operation or potential problems 

with the ControlKeeper T. Normal operation includes the 

following LED states.

Status LED: 

The Status LED will flash ON and OFF 

continuously under normal operation. The LED is an 

indication of microprocessor health. If the LED is ON or 

OFF all the time, please use the soft reset button on the 

controller. If the LED does not resume normal flashing 

state, contact technical support.

Digital Switch LEDs: 

These LEDs, labeled CAN-TX and 

CAN-RX, will flash when digital switch information is being 

passed back and forth between the GDS-I device and 

the ControlKeeper

 

T. The CAN-RX LED flashes when the 

controller is receiving data from the Digital Switch BUS. The 

CAN-TX LED flashes when the controller is sending data to 

the Digital Switch BUS.

Power LED: 

The POWER LED indicates that the 

ControlKeeper

 

T is getting the proper expected voltage from 

the transformer. If this LED is not lit, there is a problem 

with power to the board. Please contact technical support 

for further details.

Figure 12.  Status LED Indicators CKT

Network LED: 

The Network LED should flash only when 

activity is present on the network wire. If communications 

commands are not being transmitted over the network wire 

from the Keeper Enterprise Software or broadcast switches 

and this LED is flickering, ON constant or flashing, it is an 

indication of noise on the network wire that may interfere 

with proper system operation. Please check all network wir-

ing carefully for shorts to conduit ground if this condition 

exists. Contact technical support for further troubleshooting 

help.

RSC Status LEDs

There are two LED indicators on the RSC as well as an LED 

next to each side of the RSC Override Switch. Please refer 

to Figure 13 for the location of these LEDs

Figure 13.  RSC Status LEDs

Status LED: 

The Status LED will flash ON and OFF 

continuously under normal operation. The normal pattern 

of flashing is ON for approximately 4 seconds then OFF for 

approximately 1 second then back ON again. In addition to 

this blink pattern, the LED will blink erratically when there 

Summary of Contents for CKT LB

Page 1: ...on when performing maintenance on this equipment Failure to follow this warning and proper safety procedures could result in severe injury or death and or damage to the equipment 8 Document all wiring...

Page 2: ...e brought into the cabinet from the top section there is a knockout reserved on the left side which will allow conduit to be run from the top of the enclosure into the low voltage wiring area Failure...

Page 3: ...with the lighting control system The ControlKeeper T enclosures are capable of powering a number of these devices Please refer to the chart below for details on how many devices the transformer can s...

Page 4: ...10 to enable 24 VDC to the low voltage switch channels See Figure 3 for location Figure 3 Digital Switch Gateway Wiring Detail Analog Input Wiring This section describes the wiring for analog input de...

Page 5: ...using Belden 9841 or 89841 leave all shields disconnected making certain that shield is not exposed These wire types will be connected to a special terminal block on the right side of the controller...

Page 6: ...hat comes out of the top of the CKT logic panel into the Relay Stack Controller Card RSC located at the bottom of the enclosure This connection should be made to the left most terminal on the RSC See...

Page 7: ...means of overriding relays ON or OFF without the need of the logic board in place First there are individual relay override buttons for each relay located on the relay hardware Second there is an all...

Page 8: ...se the soft reset button on the controller If the LED does not resume normal flashing state contact technical support Digital Switch LEDs These LEDs labeled CAN TX and CAN RX will flash when digital s...

Page 9: ...all the time check that the Power LED on the RSC is lit then use the reset button on the ControlKeeper T and see if the LED resumes the blinking state If the Relay Status LED does not resume its norma...

Page 10: ...t to touch anywhere else on the screen If more than a minute goes by without all four corners being touched or if you touch anything other than the four corners you will leave the memory clear functio...

Page 11: ...ion 11 Network Termination Jumper 12 LCD Display Contrast Tuning Potentiometer 13 Local Remote Jumpers 14 Remote Power Connector DC Gnd 24V 15 Contact Input Switch Wiring Channels 16 Relay Stack Contr...

Page 12: ...le ControlKeeper T 1 Enlevez les d tritus et les rognures de m tal dans le bo tier 2 Assurez vous qu aucun c blage haute tension n est expos De plus il ne doit pas y avoir de c blage haute tension da...

Page 13: ...C blage des interrupteurs d entr e par contact Cette section d crit le c blage pour les dispositifs de fermeture contact sec Il y a trente deux bornes d entr e pour les interrupteurs sur le fond du C...

Page 14: ...tifs veuillez communiquer avec le soutien technique pour conna tre les limites exactes sur le nombre de dispositifs pouvant tre aliment par la carte logique C blage des capteurs de photod tection et d...

Page 15: ...es J9 et J10 pour mettre en service 24 V c c aux canaux d interrupteur basse tension Voir figure 3 pour l emplacement Figure 3 D tails du c blage de la passerelle pour interrupteurs num riques C blage...

Page 16: ...a carte logique 3 Tout le c blage basse tension doit tre achemin dans un tuyau s par du c blage de tension de ligne 4 V rifiez l absence de courts circuits de la mise la terre c a dans tous les c blag...

Page 17: ...d alimentation raccord en plastique blanc auquel six fils sont rattach s qui passe par le dessus du panneau de logique du ControlKeeper T pour rejoindre la carte de contr leur de relais en s rie RSC...

Page 18: ...tilisant ces m canismes de prise en charge sans que le panneau de logique ne soit en place Notes de prise en charge de relais individuel Les prises en charge de relais individuels sont situ es dans la...

Page 19: ...nique pour plus de d tails R seau DEL Le R seau DEL devrait uniquement clignoter quand une activit est pr sente sur le c blage r seau Si des instructions de communications ne sont pas transmises par l...

Page 20: ...muniquer avec le Soutien technique pour r soudre ce probl me Indicateur DEL de relais L indicateur DEL de relais indique que le relais est mis sous tension ou hors tension Si le relais a t mis sous te...

Page 21: ...n d affichage un coin apr s l autre dans le sens des aiguilles d une montre en vous assurant de ne pas toucher d autres endroits sur l cran S il se passe plus d une minute sans que les quatre coins so...

Page 22: ...son de r seau 12 Potentiom tre de r glage de contraste de l affichage LCD 13 Bretelles locales distance 14 Connexion alimentation distance DC Gnd 24 V 15 Canaux de c blage interrupteur d entr e contac...

Page 23: ...siones graves o la muerte o da os en el equipo 8 Documente todas las terminaciones y ubicaciones del cableado y del dispositivo de modo que los dispositivos se puedan configurar y programar correctame...

Page 24: ...lojamiento hacia el rea de conexiones de bajo voltaje De no separar los cables de alto y bajo voltaje se pueden generar interferencias en la funci n de la placa l gica 3 Todos los cables de bajo volta...

Page 25: ...olador Adem s si los tipos de interruptores son combinados el incandescente y el LED en el mismo controlador estas cantidades cambiar n Contacte a Soporte T cnico con los n meros y tipos de entradas q...

Page 26: ...de 24 VCC de entrada del interruptor 4 Conecte el hilo NEGRO del cable al terminal de conexi n a tierra en la parte trasera del GDS I y al terminal de conexi n a tierra del conector de alimentaci n re...

Page 27: ...ierdo o desde su superficie inferior Si se deben ingresar cables de bajo voltaje en el recinto desde la parte superior hay un expulsor reservado en el lateral izquierdo que permitir pasar el conducto...

Page 28: ...rese de limpiar el panel para que no queden residuos o fragmentos Aseg rese de que no hayan quedado fragmentos atrapados entre la placa del circuito y el alojamiento 2 Aseg rese de que no queden cabl...

Page 29: ...er T tiene dos modos de anular el encendido o el apagado de los rel s sin la necesidad de una placa l gica En primer lugar hay dos botones de anulaci n individual de rel s para cada rel ubicado en su...

Page 30: ...parpadear n cuando se pase informaci n del interruptor digital desde y hacia el dispositivo GDS I y el ControlKeeper T El LED CAN RX parpadea cuando el controlador recibe datos del BUS del interrupto...

Page 31: ...parpadeo Si el LED de estado del rel no retoma su estado de parpadeo normal luego del reinicio del ControlKeeper T contacte a Soporte T cnico Si el LED parpadea de manera continua sin parar ello indi...

Page 32: ...do de las agujas del reloj asegur ndose de no tocar en ninguna otra parte de la pantalla Si pasa m s de un minuto sin que se toquen todas las esquinas o si toca otra cosa saldr de la funci n de elimin...

Page 33: ...l para el bloque de rel 26 Interruptor de anulaci n individual de rel s 27 Indicador de estado del rel 28 LED de estado de la tarjeta de rel 29 Conexi n desde el carril central hacia el RSC 1 LED de e...

Page 34: ......

Page 35: ......

Page 36: ...sont la propri t de leur propri taire respectif Eaton es una marca comercial registrada Todas las marcas comerciales son propiedad de sus respectivos propietarios WARRANTIES AND LIMITATION OF LIABILI...

Reviews: