background image

Reading Performance Charts

Assume that a job requires a belt drive roof exhauster
to move 1000 cfm against 0.25 in. Ps. Refer to the
performance model at the bottom of this page. Start at
the top of the chart with the 0.25 in. Ps column. (All
numbers in this column correspond to .25 in. Ps.) Now
follow the column downward until a value is found that
slightly exceeds 1000 cfm. In this case, 1012 cfm is the
first box that meets the requirements.

Note: Notice that each performance box is divided into
3 smaller boxes. The numbers refer to cfm, Sones and
Bhp.

Example:

At this performance point, the sone value is 11.1 and
the fan Bhp required is 0.16. Now by following the row
to the left, we can determine fan rpm and fan model.
In this case, the fan rpm is 1510 and the model is
GB-090-4 which has a 1/4 hp motor.

Notice that the GB-090-4 is not the only model to
choose from. If we follow the 0.250 in. Ps column down
further, we find a performance point at 1010 cfm. 

At this point, the sone value is 7.9 and the Bhp is 0.14.
Following across to the left we find the rpm to be 1355.
The model is GB-101-4-R1, which also has a 1/4 hp
motor.

Both the GB-090-4 and the GB-101-4-R1 will perform
the air movement task equally as well. However, the
sound generated by the fan may have to be
considered. Compare the sone values: 7.9 sones for the
GB-101 and 11.1 for the GB-090. The GB-101 is about
30% quieter. Where a low sound fan is required, the
GB-101 would be a better selection. If loudness is not a
factor, the GB-090 would be a better selection because
it is less expensive.

Another possibility for this particular selection is a
GB-100-4-R2. Even though there is no performance
box showing close to 1000 cfm, there are two
performance boxes that bracket 1000 cfm. At 921 cfm
the fan will be running at 1260 rpm. At 1269 cfm the fan
will be running at 1635 rpm. Therefore, there is an rpm
for this model that will correspond to 1000 cfm
(obviously somewhere within the 1260-1635 rpm
range). As with all Greenheck belt drive fans,
intermediate cfm values are easily achieved by
adjusting the motor pulley (see illustration on next
page). 

The most important part of selecting a fan is the ability
to read the performance charts. Most of the
performance charts in the catalog are similar and are
read in the same manner. Models RSF and BCF are

exceptions to this rule. The selection procedure for
these models is handled separately. Direct drive and
belt drive fans are also addressed separately.

Belt Drive Selection

CFM

Sone         Bhp

1012

11.1          0.16

1030

957

884

807

725

632

10.1

0.11

9.9

0.12

9.6

0.12

9.3

0.12

8.8

0.13

8.5

0.13

1144

1078

1012

946

875

800

720

607

11.4

0.15

11.2

0.16

11.1

0.16

10.7

0.17

10.4

0.17

10.0

0.17

9.8

0.17

9.5

0.17

1295

1237

1179

1121

1061

999

934

866

785

13.4

0.22

13.3

0.23

13.2

0.23

13.0

0.24

12.7

0.24

12.4

0.25

12.1

0.25

11.8

0.25

11.6

0.25

906

818

731

607

6.0

0.060

5.4

0.065

5.0

0.070

4.3

0.070

1148

1077

1010

943

856

739

8.5

0.12

8.1

0.13

7.9

0.14

7.8

0.14

7.2

0.14

6.8

0.14

1067

991

921

840

735

385

7.6

0.099

7.1

0.104

6.8

0.112

6.5

0.115

5.9

0.115

4.4

0.083

1385

1325

1269

1214

1161

1094

1019

928

792

11.1

0.22

10.8

0.22

10.4

0.23

10.2

0.24

9.8

0.25

9.3

0.25

8.9

0.25

8.4

0.25

7.8

0.24

1525

1471

1418

1367

1320

1270

1208

1141

1064

13.2

0.29

12.8

0.30

12.5

0.30

12.3

0.31

12.2

0.33

11.3

0.33

10.8

0.33

10.6

0.33

10.1

0.33

STATIC PRESSURE / CAPACITY

0.000

0.125

0.250

0.375

0.500

0.625

0.750

0.875

1.000

Sone Bhp Sone Bhp Sone Bhp Sone

Bhp Sone

Bhp Sone

Bhp Sone

Bhp Sone

Bhp Sone

Bhp

MODEL

(rpm RANGE)

RPM

TS

1360

3983

1510

4422

1710

5008

1070

3116

1355

3946

1260

3669

1635

4761

1800

5242

hp

GB-090-4

(1290-1710)

GB-101-4-R1

(1020-1400)

GB-101-3

GB-101-4-R2

(1260-1635)

1/4

1/4

1/4

1/3

5

Table 2

Summary of Contents for 240XP-CUB

Page 1: ...Fan Selection Application Based Selection Performance Theory...

Page 2: ...e and static pressure This section also interprets Greenheck model numbers and illustrates the relationship between fan speed and airflow Section Two covers the basics of fan selection determining the...

Page 3: ...N FAN APPLICATION Basic Overview 9 Commercial Kitchen Ventilation 10 General Commercial Ventilation 12 High Static Pressure Ventilation 15 Determining CFM 16 Determining Static Pressure 17 Sound Level...

Page 4: ...B Model is G rpm is 1140 Nominal Wheel Dia 12 in The table below lists model designation suffixes for motor horsepower and fan rpm Belt Drive Direct Drive Suffix Motor hp Suffix Fan rpm 6 1 6 A 1725 4...

Page 5: ...1 cfm the fan will be running at 1260 rpm At 1269 cfm the fan will be running at 1635 rpm Therefore there is an rpm for this model that will correspond to 1000 cfm obviously somewhere within the 1260...

Page 6: ...rpm D 1300 rpm G and 1050 rpm E Changing a motor lead is all that is necessary to change speeds When selecting a model with 3 speed motors it is recommended that the G speed be chosen whenever possib...

Page 7: ...1 2 hp motor RSF 90 4 1 4 hp motor is not recommended for this job Matching a Specification There will be times when a Greenheck model will have to be matched to a competing manufacturer s unit To ai...

Page 8: ...WD CW Fumex WFX Domex WX WA WB PDU W PW CWD VWDK VWDB CWD CWF CDU WDC DU CWB GWB ACWB CWB TWB Fumex WFXB Domex WCB WLB PNU W PWB NBTD NBRTD UL 762 VWBK VWBB CWB CBU WBC NCA SP Gemini GC Zephyr Z RA TD...

Page 9: ...fan model and the air volume flow rate cfm Other considerations include the resistance to airflow static pressure or Ps and sound produced by the fan Sones Occasionally a customer will require a fan t...

Page 10: ...2 listed for restaurant applications and for operation with air temperatures up to 300 F Recommended Supply Fans The above models are designed to provide efficient economical make up air to replenish...

Page 11: ...s The National Fire Protection Association specifies minimum distance criteria for restaurant exhaust and supply fans as shown below 10 ft Horizontal Separation 1 Roof deck to top of exhaust fan windb...

Page 12: ...sting relatively clean air at temperatures up to 130 F Motors are out of the airstream Direct drive sizes 60 95 are equipped with 3 speed motors for maximum airflow flexibility All direct drive units...

Page 13: ...Typical Commercial Ventilation Installations 13...

Page 14: ...ount as well as exhaust or supply However because the motors are mounted in the airstream these models are not recommended for temperatures above 110 F Model SB Belt Drive Propeller Sidewall 3 600 85...

Page 15: ...generated by long or complex duct systems especially when capture hoods are present Both models can be used for either exhaust or supply Model SWB is designed to be mounted indoors or outdoors while...

Page 16: ...rmal area usage select a lower number in the range to change the air more quickly For moderate climates with lighter usages select a higher number in the range To determine the cfm required to adequat...

Page 17: ...an be used for estimating static pressure To calculate the system losses one must know the ductwork system configuration see Ductwork figure This duct is sized for air velocities of 1400 feet per minu...

Page 18: ...8 0 76 15 9 0 77 14 9 0 77 14 8 0 77 14 7 0 78 2318 2104 1875 1587 8 9 0 18 8 5 0 19 8 3 0 19 7 8 0 19 2555 2359 2162 1932 1624 10 6 0 24 10 1 0 25 9 7 0 26 9 4 0 26 8 8 0 25 2909 2737 2567 2382 2176...

Page 19: ...essure levels For example a sound level of 10 sones is twice as loud as 5 sones Refer to the Suggested Limits for Room Loudness chart to determine the acceptable sone range for the application As a ge...

Page 20: ...w into the fan Wheel Rotation A common problem is wheel rotation in the wrong direction For centrifugal fans incorrect wheel rotation will provide some airflow However the airflow will be far below th...

Page 21: ...application The information in this section is useful once the fan has been selected and installed on the job The fan curves and system resistance curves below will help to solve fan performance probl...

Page 22: ...ossible to move 2000 cfm at only 0 25 in Ps For any given system every cfm requires a unique Ps This series of cfm Ps points forms a system resistance curve such as the one above Once the system resis...

Page 23: ...that as we doubled our airflow from 1000 cfm to 2000 cfm the Ps went up from 0 25 in to 1 0 in It must be kept in mind that we are not changing the system only increasing fan speed Therefore we must...

Page 24: ...s in those sections on how to apply these equations The third equation relates horsepower to rpm The change in horsepower can be determined when the rpm is increased by 25 This is shown below BhpNew 1...

Reviews: