background image

Table 1 lists and describes all of the BACnet data points associated with the controller inside the actuator of BACnet 

enabled AMD-TD series dampers .

Name

Type

#

Access

Description

Greenheck AMD-TD

AI

1

C

Displays the application version

AirflowSetpoint

AI

2

C

Displays the real-time setpoint in cfm

CurrentAirflow

AI

3

C

Displays the real-time volumetric airflow rate in cfm

AirVelocity

AI

4

C

Displays the real-time air velocity in fpm

DamperPosition

AI

5

C

Displays the real-time damper position as a percentage (0% - fully 
closed; 100% fully open)

MaxCFMSetpoint

AI

6

C

Displays the maximum volumetric airflow rate in cfm .  This value is 
a function of the value selected for "Maximum FPM" .  (Max CFM 
Setpoint = Damper Area * Maximum FPM) . 

DamperArea

AV

1

C

Represents the nominal damper face area in square feet .  Set by 
the factory .

MinimumFPMSetpoint

AV

2

C

Represents the minimum allowable velocity setpoint in fpm .  If the 
actuator receives a setpoint below the "Minimum FPM Setpoint" 
the setpoint will be set to zero .  The factory default value is 100 
fpm .   

BACnet Setpoint

AV

3

C

When the Setpoint Source is set to BACnet this variable 
establishes the unit's setpoint .  When the Damper Mode is set 
to Flow the BACnet Setpoint is a percentage of the MaxCFM 
Setpoint .  When the Damper Mode is set to Position the BACnet 
Setpoint is the percentage the damper is open .  When the Setpoint 
Source is set not set to BACnet this variable has no impact on 
controlling the damper .  

SafetyStatus

BI

1

C

Represents the status of the safety circuit . Inactive = Open/Failure; 
Active  = Closed/OK

MaximumFPM

MV

1

C

Represents the maximum setpoint velocity in fpm .  The value this 
variable is set to corresponds to a 10 VDC input to the actuator .  
This value is set at the factory based on maximum velocity that 
was selected at the time the unit was ordered . 1 = 500 fpm; = 1000 
fpm; 3 = 1500 fpm; 4 = 2000 fpm; 5 = 2500 fpm; 6 = 3000 fpm; 7 = 
3500 fpm; 8 = 4000 fpm

DamperMode

MV

2

C

Establishes the mode of operation for the actuator .  When in flow 
control mode the actuator will view the setpoint as a target cfm 
to maintain .  When in position control mode the actuator will view 
the setpoint percentage as a position to drive to (0% fully closed, 
100% fully open) .  Whether the actuator is in Flow or Position 
control mode the source of the setpoint will be determined by the 
Setpoint Source variable .  1 = Flow; 2 = Position

SetpointSource

MV

3

C

When set to BACnet the actuator uses the BACnet variable as 
the setpoint .  When set to Local AI it uses the actuator's second 
analog input (S2) as the setpoint .  When set to Zth the actuator 
uses a handheld Zth module to establish the setpoint . 1 = BACnet; 
2 = Local AI; 3 = ZTH

AI - Analog Input
AO - Analog Output
AV - Analog Value
BI - Binary Input
BO - Binary Output
BV - Binary Value

MI - Multi-State Input
MO - Multi-State Output
MV - Multi-State Value
R - ReadOnly
W - Writable
C -  Commandable (Contains 

Priority Array)

BACNet Data Point List

7

Air Measuring Dampers: AMD-XX-TD Series

Summary of Contents for AMD-42-TD

Page 1: ...ge If damage is found record all necessary information on the bill of lading and file a claim with the final carrier Check to be sure that all parts of the shipment including accessories are accounted for Dampers must be kept dry and clean Indoor storage and protection from dirt dust and the weather is ideal Do not store at temperatures in excess of 100 F 37 C 1 Air Measuring Dampers AMD xx TD Ser...

Page 2: ...n materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray Spreader Bar Attachments Multi section dampers 6 Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet 1 5m of the damper Excessive dirt or foreign material deposits on the damper can cause excess...

Page 3: ...ners of each section 5 Damper blades axles and linkage must operate without binding Before system operation you can cycle dampers after installation to assure proper operation On multiple section assemblies all sections should open and close simultaneously Setup and Operation for AMD xx TD Series Damper All AMD xx TD s are supplied with a Vari Green airflow rate transmitter that is factory wired t...

Page 4: ...ured Velocity Max Velocity Measured Voltage 10 Measured Velocity 2 000 3 5 10 Measured Velocity 700 fpm and Measured CFM Measured Velocity Area Measured CFM 700 fpm 4 ft2 Measured CFM 2 800 cfm AMD xx TD Series Ordered with a Factory Supplied Controller When you order a factory supplied controller it comes with a Greenheck exclusive VAF24 BAC GTD actuator which has the controller integrate inside ...

Page 5: ...t it maintains a desired cfm setpoint The setpoint is established by the BACnetSetpoint datapoint Table 1 lists all of the BACnet datapoints The BACnet Setpoint is a percentage of the MaxCFMSetpoint datapoint which is set at the factory based on the maximum velocity which is selected at the time the unit is ordered Example 3 Determine the BACnet setpoint for a 24 in x 24 in AMD with a maximum velo...

Page 6: ...tions Right click on the Local Area Connection and select Properties Access IP Address Settings 1 Select Internet Protocol Windows 7 or 8 Select Internet Protocol Version 4 TCP IPv4 the click on Properties Windows XP Select Internet Protocol TCP IP the select Properties 2 Change the IP Address to the value shown below Then hit the Tab key and the Subnet mask will populate Then click OK Access the ...

Page 7: ...oint Source is set not set to BACnet this variable has no impact on controlling the damper SafetyStatus BI 1 C Represents the status of the safety circuit Inactive Open Failure Active Closed OK MaximumFPM MV 1 C Represents the maximum setpoint velocity in fpm The value this variable is set to corresponds to a 10 VDC input to the actuator This value is set at the factory based on maximum velocity t...

Page 8: ...ress is done via the integrated web server BACnet Standard Device Profile BACnet Application Specific Controller B ASC BACnet Interoperability Building Blocks supported Data Sharing ReadProperty B DS RP B Data Sharing ReadPropertyMultiple B DS RPM B Data Sharing WriteProperty B DS WP B Device Management DynamicDeviceBinding B DM DDB B Device Management DynamicObjectBinding B DM DOB B Device Manage...

Page 9: ...meout Number_Of_APDU_Retries Max_Master 2 Max_Info_Frames2 Multistate Input Description State_Text Multistate Value Description State_Text Relinquish_Default1 Priority_Array1 Present_Value Multistate Output Description State_Text Relinquish_Default1 Priority_Array1 Present_Value The properties Object_Name and Location of the Device Object support up to 255 characters all other character strings ar...

Page 10: ...bow Without Vanes 1 2D 1D Round Sweep Elbow Optimal Placement for AMD xx TD Damper Series Fans 2D Centrifugal Fan Discharge 3 4D Centrifugal Fan Inlet 3D Vane Axial Fan Discharge 1D Vane Axial Fan Inlet 10 Air Measuring Dampers AMD XX TD Series ...

Page 11: ...Series Takeoffs 1 5D Branch Takeoff 2 1D Branch Takeoff B1 Transitions 1 2D α α Transition 1 Bellmouth Inlets 1 2D α α Transition 3 Circular Duct D Duct Diameter 4 x Width x Height Rectangular Duct D 11 Air Measuring Dampers AMD XX TD Series ...

Page 12: ...the linkage where required Minimum Installation Requirements When installing the AMD xx TD the installation should match as closely as possible to one othe examples shown on pages 10 and 11 Failure to match the installation examples may negatively affect the performance and accuracy of the AMD xx TD Avoid locating the AMD xx TD where they will be exposed to condensing moisture such as downstream o...

Reviews: