background image

Preparation of Openings

•  Corridor dampers are rated in ceiling constructions with a fire resistance rating of one hour. 
•  Frame corridor openings as shown below. Maximum size of opening is 24 in. x 24 in. (610 mm x 610 mm). 

(

see Figure 1 & 2

).

•  Corridor ceiling must be covered with a minimum of one sheet of 

5

8

 in. UL rated gypsum board on both sides.

•  All construction and fasteners must meet the requirements of the appropriate corridor ceiling design. Gypsum 

panels should be attached, 12 in. (305 mm) O.C. maximum, to all stud and runner flanges surrounding opening 
with fasteners as designated by the appropriate corridor ceiling design.  (See UL Fire Resistance Directory) and/
or local codes.

Figure 1

Steel

studs

2 in. x 4 in. 
(nominal)

 wood studs

Steel Stud Assembly

Wood Stud Assembly

24 in. 
max.

24 in. o.c. max.

24 in.
 max.

24 in. o.c. max.

Opening lined 
with UL rated
5/8 in. gypsum 
board

Figure 2

Steel

studs

2 in. x 4 in. 
(nominal)

 wood studs

Steel Stud Assembly

Wood Stud Assembly

24 in. 
max.

24 in. o.c. max.

24 in.
 max.

24 in. o.c. max.

Opening lined 
with UL rated
5/8 in. gypsum 
board

Clearances Required Between Corridor Damper Sleeves and Ceiling 

Openings

The interior dimension of the prepared ceiling opening should be 

1

4

 in. (6 mm) larger than the overall size of the 

damper and sleeve assembly.

These are total clearances (ignoring fastener heads) and do not need to be spaced equally around the damper.

Maximum Assembly Table

Damper Model

Maximum Single

Section Size

(inches)

CFSD-211, -212

24 x 24

Horizontal Mount

CFSD Series

3

®

Summary of Contents for CFSD-211

Page 1: ...at temperatures in excess of 100 F 38 C SAFETY WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Installation Supplements 2 Electrical Guidelines 2 Pre Installation Guidelines...

Page 2: ...tallations can cause excessive leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and after installation Examples of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be s...

Page 3: ...tance Directory and or local codes Figure 1 Steel studs 2 in x 4 in nominal wood studs Steel Stud Assembly Wood Stud Assembly 24 in max 24 in max 24 in o c max Opening lined with UL rated 5 8 in gypsum board Figure 2 Steel studs 2 in x 4 in nominal wood studs Steel Stud Assembly Wood Stud Assembly 24 in max 24 in o c max 24 in max 24 in o c max Opening lined with UL rated 5 8 in gypsum board Clear...

Page 4: ...imum of two attachments are required on each side top and bottom The angles may be attached to each other at the corners Retaining angles must cover the clearance space between the sleeve and the ceiling opening Retaining angles See Section 3 2 in x 4 in wood or 2 in x 2 1 2 in steel studs 1 in x 2 1 2 in 16 ga angles either inside or outside of sleeve Grille supplied by others Opening lined with ...

Page 5: ...0 19 mm sheet metal screws on each side and on the bottom may be used The screws should be located in the center of the slip pocket and penetrating both sides of the slip pocket Dampers up to 20 inches 508 mm high may use transverse joints on the top and bottom and Drive Slip joints see Figure 6 on the sides Plain S Slip Hemmed S Slip Double S Slip Inside Slip Joint Standing S Standing S Alt Stand...

Page 6: ... 5 5 5 6 Std Clip Length C L Duct 60 Duct 4 Reqd 48 Duct 3 Reqd 36 Duct 3 Reqd 24 Duct 2 Reqd 18 Duct Smaller 1 Reqd Clip Spacing Typical TDC TDF joint 6 Figure 10 Manufactured Flanged System Breakaway Connections Flanged connection systems manufactured by Ductmate Durodyne Ward MEZ and Nexus are approved as breakaway connections when installed as illustrated see Figure 9 Figure 13 Metal cleat met...

Page 7: ...ndicator option contains two single pole single throw switches used to indicate the damper blade position The switches provide a positive open and closed signal and can be used in conjunction with remote indicator lights Refer to Figure 14 for wiring of the OCI option RRL OCI The RRL OCI performs the function of an RRL and OCI see description above Refer to Figure 15 for wiring of the RRL OCI opti...

Page 8: ...ls Adjust frame such that it is square and plumb Actuator linkage loose Close damper disconnect power adjust and tighten linkage Defective motor Replace Screws in damper linkage Damper installed too far into wall Move out to line as designated on damper label Contaminants on damper Clean with a non oil based solvent see Damper Maintenance RRL or TOR sensor tripped Heat Push reset button located on...

Reviews: