background image

Duct to Sleeve Connection

Sleeve Gauge and Connection Type Requirements

Dampers are supplied with sleeves and actuators from the factory and can be installed without the need for 
additional field installed sleeves. Damper sleeves should be a minimum of 24 ga. (0.6 mm). The sleeve thickness 
must also not be less than the gauge of the connecting duct. If duct gauge is 16 ga. (1.5 mm) or greater, the 
breakaway connection is rigid.

Approved Breakaway Connections

All breakaway connections described below may utilize the following duct sealants: PA2084T duct sealant adhesive 
manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymerics, Grey Pookie, 
Ductmate PROseal®, or CL Ward S Seal in accordance with SMACNA recommendations.

Transverse Joints

The transverse joints shown below are approved as breakaway connections.
  •  A maximum of two #10 (19 mm) sheet metal screws on each side and on the bottom may be used. The screws 

should be located in the center of the slip pocket and penetrating both sides of the slip pocket.

  •  Dampers up to 20 inches (508 mm) high may use transverse joints on the top and bottom and Drive Slip joints 

(

see Figure 6

) on the sides.

Plain “S” Slip           Hemmed “S” Slip                 Double “S” Slip

Inside Slip Joint             Standing “S”               Standing “S” (Alt.)

 Standing “S” (Alt.)                Standing “S”                   Standing “S”

                                           (Bar Reinforced)             (Angle Reinforced)

Figure 6

Drive Slip Joint

Figure 7

Round and Oval Duct Breakaway Connections

Round or flat oval ducts connected to Type R or O damper collars shall be attached with #10 (19 mm) sheet metal 
screws as follows:
  •  Ducts to 22 in. (558 mm) wide (or dia.) and smaller shall have three screws.
  •  Ducts larger than 22 in. (558 mm) wide (or dia.) up to and including 36 in. (914 mm) wide (or dia.) shall have five 

screws.

Wall or Floo

r

Sleeve

Duct

Damper

Type B

Wall or Floo

r

Sleeve

Duct

Damper

Type R, O

Type R and O
factory furnished
duct collars qualify
as breakaway
connections.

Figure 8: Type R and O Transition

CFSD Series

5

®

Summary of Contents for CFSD-211

Page 1: ...at temperatures in excess of 100 F 38 C SAFETY WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Installation Supplements 2 Electrical Guidelines 2 Pre Installation Guidelines...

Page 2: ...tallations can cause excessive leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and after installation Examples of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be s...

Page 3: ...tance Directory and or local codes Figure 1 Steel studs 2 in x 4 in nominal wood studs Steel Stud Assembly Wood Stud Assembly 24 in max 24 in max 24 in o c max Opening lined with UL rated 5 8 in gypsum board Figure 2 Steel studs 2 in x 4 in nominal wood studs Steel Stud Assembly Wood Stud Assembly 24 in max 24 in o c max 24 in max 24 in o c max Opening lined with UL rated 5 8 in gypsum board Clear...

Page 4: ...imum of two attachments are required on each side top and bottom The angles may be attached to each other at the corners Retaining angles must cover the clearance space between the sleeve and the ceiling opening Retaining angles See Section 3 2 in x 4 in wood or 2 in x 2 1 2 in steel studs 1 in x 2 1 2 in 16 ga angles either inside or outside of sleeve Grille supplied by others Opening lined with ...

Page 5: ...0 19 mm sheet metal screws on each side and on the bottom may be used The screws should be located in the center of the slip pocket and penetrating both sides of the slip pocket Dampers up to 20 inches 508 mm high may use transverse joints on the top and bottom and Drive Slip joints see Figure 6 on the sides Plain S Slip Hemmed S Slip Double S Slip Inside Slip Joint Standing S Standing S Alt Stand...

Page 6: ... 5 5 5 6 Std Clip Length C L Duct 60 Duct 4 Reqd 48 Duct 3 Reqd 36 Duct 3 Reqd 24 Duct 2 Reqd 18 Duct Smaller 1 Reqd Clip Spacing Typical TDC TDF joint 6 Figure 10 Manufactured Flanged System Breakaway Connections Flanged connection systems manufactured by Ductmate Durodyne Ward MEZ and Nexus are approved as breakaway connections when installed as illustrated see Figure 9 Figure 13 Metal cleat met...

Page 7: ...ndicator option contains two single pole single throw switches used to indicate the damper blade position The switches provide a positive open and closed signal and can be used in conjunction with remote indicator lights Refer to Figure 14 for wiring of the OCI option RRL OCI The RRL OCI performs the function of an RRL and OCI see description above Refer to Figure 15 for wiring of the RRL OCI opti...

Page 8: ...ls Adjust frame such that it is square and plumb Actuator linkage loose Close damper disconnect power adjust and tighten linkage Defective motor Replace Screws in damper linkage Damper installed too far into wall Move out to line as designated on damper label Contaminants on damper Clean with a non oil based solvent see Damper Maintenance RRL or TOR sensor tripped Heat Push reset button located on...

Reviews: