background image

Damper Maintenance

Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use 
mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and 
jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
  • The latest editions of NFPA 80, 90A, 92, 101, 105, UL864, AMCA 503-03 and local codes.
  • Actuator manufacturer recommendations.

Damper Troubleshooting

The following is a possible cause and correction list for common concerns with the dampers.

Symptom

Possible Cause

Corrective Action

Damper does not fully 
open and/or close

Frame is 'racked' causing blades to bind 
on jamb seals

Adjust frame such that it is square and plumb

Actuator linkage loose

Close damper, disconnect power, adjust and tighten 
linkage

Defective motor

Replace

Screws in damper linkage

Damper installed too far into wall. Move out to line as 
designated on damper label

Contaminants on damper

Clean with a non-oil based solvent (see Damper 
Maintenance)

RRL or TOR sensor 
tripped

Heat

Push reset button located on backside of RRL or TOR

Damper does not 
operate

No power supplied to the actuator

Add power supply

461335 • CFSD Series, Rev. 16, January 2022 

Copyright 2022 © Greenheck Fan Corporation

8

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications 
without notice.

Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature 
section of the website at Greenheck.com/Resources/Library/Literature.

®

Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com

Our Commitment

Summary of Contents for CFSD-211

Page 1: ...at temperatures in excess of 100 F 38 C SAFETY WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Installation Supplements 2 Electrical Guidelines 2 Pre Installation Guidelines...

Page 2: ...tallations can cause excessive leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and after installation Examples of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be s...

Page 3: ...tance Directory and or local codes Figure 1 Steel studs 2 in x 4 in nominal wood studs Steel Stud Assembly Wood Stud Assembly 24 in max 24 in max 24 in o c max Opening lined with UL rated 5 8 in gypsum board Figure 2 Steel studs 2 in x 4 in nominal wood studs Steel Stud Assembly Wood Stud Assembly 24 in max 24 in o c max 24 in max 24 in o c max Opening lined with UL rated 5 8 in gypsum board Clear...

Page 4: ...imum of two attachments are required on each side top and bottom The angles may be attached to each other at the corners Retaining angles must cover the clearance space between the sleeve and the ceiling opening Retaining angles See Section 3 2 in x 4 in wood or 2 in x 2 1 2 in steel studs 1 in x 2 1 2 in 16 ga angles either inside or outside of sleeve Grille supplied by others Opening lined with ...

Page 5: ...0 19 mm sheet metal screws on each side and on the bottom may be used The screws should be located in the center of the slip pocket and penetrating both sides of the slip pocket Dampers up to 20 inches 508 mm high may use transverse joints on the top and bottom and Drive Slip joints see Figure 6 on the sides Plain S Slip Hemmed S Slip Double S Slip Inside Slip Joint Standing S Standing S Alt Stand...

Page 6: ... 5 5 5 6 Std Clip Length C L Duct 60 Duct 4 Reqd 48 Duct 3 Reqd 36 Duct 3 Reqd 24 Duct 2 Reqd 18 Duct Smaller 1 Reqd Clip Spacing Typical TDC TDF joint 6 Figure 10 Manufactured Flanged System Breakaway Connections Flanged connection systems manufactured by Ductmate Durodyne Ward MEZ and Nexus are approved as breakaway connections when installed as illustrated see Figure 9 Figure 13 Metal cleat met...

Page 7: ...ndicator option contains two single pole single throw switches used to indicate the damper blade position The switches provide a positive open and closed signal and can be used in conjunction with remote indicator lights Refer to Figure 14 for wiring of the OCI option RRL OCI The RRL OCI performs the function of an RRL and OCI see description above Refer to Figure 15 for wiring of the RRL OCI opti...

Page 8: ...ls Adjust frame such that it is square and plumb Actuator linkage loose Close damper disconnect power adjust and tighten linkage Defective motor Replace Screws in damper linkage Damper installed too far into wall Move out to line as designated on damper label Contaminants on damper Clean with a non oil based solvent see Damper Maintenance RRL or TOR sensor tripped Heat Push reset button located on...

Reviews: