background image

“UL CLASSIFIED (see complete marking on 
product)”
“UL CLASSIFIED to Canadian safety standards 

(see complete marking on product)”
 

Standard 555 (Listing #R13317)

The following items will aid in completing the damper 
installation in a timely and effective manner.
1) Check the schedules for proper damper locations 

within the building. Visually inspect the damper for 
damage and verify that the fusible link is in place 
and has not activated. Never install a fire damper 
without the proper UL approved fusible link in 
place. Visually inspect the fusible link to verify its 
not damaged. Replace link as necessary.

2) Lift or handle damper using sleeve or frame. Do not 

lift damper using blades.

3) Dampers have a label indicating the required 

mounting orientation. When the mounting 
orientation is horizontal, the 'K side' must be up. 
Care must be taken to ensure that the indicated 
orientation is adhered to.

4) Damper must be installed into duct or opening 

square and free of twist or other misalignment.

5) Damper must be kept clean and protected from dirt, 

dust and other foreign materials prior to and after 
installation. Examples of such foreign materials 
include but are not limited to: 
  a) Mortar dust 
  b) Drywall dust 
  c) Firesafing materials 
  d) Wall texture 
  e) Paint overspray

6) Damper should be sufficiently covered as to prevent 

overspray if wall texturing or spray painting will be 
performed within 5 feet of the damper.

7) Caulking is not necessary, nor is it allowed, between 

the damper sleeve and the wall or floor opening 
(annular space). However, caulking may be applied 
to the retaining angles.

8) ACCESS: Suitable access (such that the fusible 

link may be removed and the damper's blade 
stack may be reset, etc.) must be provided for 
damper inspection and servicing. Where it is not 
possible to achieve sufficient size access, it will be 
necessary to install a removable section of duct. 
(Refer to NFPA 90A).

9) The Code Authority Having Jurisdiction (AHJ) must 

evaluate and provide approval of final installation 
where variations to these instructions are 
necessary.

“K” side

W*

H*

Vertical Mount

Horizontal Mount

Stainless Steel
Closure Spring

3 11/16 in.
(94mm)

Fusible Link (replaceable)

General Information

Installation Supplements

Refer to the appropriate Greenheck installation 
supplements for special requirements 
(www.greenheck.com links are underline):
 • 

Closed Indicator Switch

 

• 

Concrete Floor with Steel Deck

 

• 

Field Installed Sleeve

 

• 

Fire Resistant Ventilated Duct Assembly

 

• 

Fusible Link Replacement

 

• 

Grille Installation

 

• 

Latch Release Tool for Fire Dampers

 

• 

Metal Stud in Shaftwall Partition

 

• 

Non-Concrete Horizontal Mount

 

• 

Quick Connect Breakaway Connection

 

• 

Sealant Supplement

 

• 

Single 3-Sided Retaining Angle Supplement

 

• 

Sleeve Extension

 

• 

Support Mullions

 

• 

ABD series

Online version to this Installations at  
www.greenheck.com.

Pre-Installation Guidelines

Curtain Fire Dampers 
Instructions

Curtain Fire Dampers

2

®

Summary of Contents for DFD 150 Series

Page 1: ...tion service or maintenance can cause property damage injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Pre Installation Guidelines 2 Preparation of Openings 3 Clearances Required Between Damper Sleeves Wall Floor Openings 4 Installing Multiple Section Assemblies 4 Maximum As...

Page 2: ... or spray painting will be performed within 5 feet of the damper 7 Caulking is not necessary nor is it allowed between the damper sleeve and the wall or floor opening annular space However caulking may be applied to the retaining angles 8 ACCESS Suitable access such that the fusible link may be removed and the damper s blade stack may be reset etc must be provided for damper inspection and servici...

Page 3: ...nt Dow Metal Stud Framing Shown Second set of studs are not required on openings 36 in x 36 in 914mm x 914mm or smaller Metal stud only 24 in 610mm O C max Detail A A Detail A A Floor Runner Ceiling Runner Notched Piece Bent Down Metal Stud Framing Shown Ceiling Runner Detail A A Floor Runner 24 in 610mm O C Max Figure 2A Metal Stud Construction Wooden Stud Construction In metal stud construction ...

Page 4: ...minmum of 1 in 25 mm For stainless steel dampers and stainless steel or galvanized sleeves 3 16 in per foot 5 mm per 3 m of damper width and height with a minimum clearance of 1 4 in 6 mm maximum of 2 in 51 mm These are total clearances ignoring fastener heads and do not need to be equally spaced around the damper Although the minimum requirements are listed above for ease of installation the foll...

Page 5: ... x 762 mm DFD 350 Vertical 36 x 36 914 mm x 914 mm Horizontal 24 x 18 610 mm x 457 mm 48 x 36 1217 mm x 914 mm 30 x 30 762 mm x 762 mm DFD 310 Vertical 36 x 36 914 mm x 914 mm Horizontal 30 x 30 762 mm x 762 mm SSDFD 150 SSDFD 350 Vertical 30 x 30 762 mm x 762 mm FD 150X Vertical or Horizontal 48 x 48 1219 mm x 1219 mm DFD 150X Vertical 36 x 36 914 mm x 914 mm Horizontal 30 x 30 762 mm x 762 mm Al...

Page 6: ...he leg of the retaining angle on the damper sleeve shall be a minimum of 11 4 in 32 mm The leg of the retaining angle on the wall floor shall be long enough to cover the annular space and overlap the wall floor by a minimum of 1 in 25 mm Retaining Angle Attachment to Sleeve Retaining angles must be attached to the damper using one or more of the following methods of attachment refer to label on ou...

Page 7: ...1 hour rated walls see UL Rated Wall Design for Additional Details Figure 8 Single Side Angle With Steel Stud Wall Angle Over Wallboard Stud or Runner Damper Sleeve Angle Fastener Two layers of 1 2 in UL Classified Gypsum Wallboard for 2 hour rated walls One layer for 1 hour rated walls see UL Rated Wall Design for Additional Details Figure 9 Single Side Angle With Wood Stud Wall Damper Sleeve Met...

Page 8: ...n 178mm Type A Type B Field installed Sleeve Damper 1 4 in minimum total clearance See Section 1 Maximum 6 in Maximum 6 in Wall or floor Wall or floor Wall or floor Damper Damper Duct Duct Duct Retaining Angles See Section 4 Sleeve See Sleeve Requirements Sleeve Sleeve On types R CR factory furnished duct collar qualifies as breakaway connection See Connecting Ducts to Fire Damper Sleeve Retaining...

Page 9: ...Precision DP1010 water base duct sealant manufactured by Design Polymerics Grey Pookie Ductmate PROseal or CL Ward S Seal in accordance with SMACNA recommendations Transverse Joints The transverse joints shown below are approved as breakaway connections A maximum of two 10 19 mm sheet metal screws on each side and on the bottom may be used The screws should be located in the center of the slip poc...

Page 10: ...facturer s instructions Duct 3 8 in bolts in corners are optional 6 in long metal cleat or 1 16 in max thickness plastic cleat 12 in c c min 1 per side Figure 18 Manufactured Flanged System Breakaway Connections Flanged connection systems manufactured by Ductmate Durodyne Ward Nexus Radiant T 35m and MEZ are approved as breakaway connections when installed as illustrated see Figure 18 Figure 22 Me...

Page 11: ...rated dampers utilizing a fusible link are required to be tested by removing the fusible link and allowing the damper to fully close and then manually reopening the damper Re install the fusible link Greenheck s life safety dampers shall not be tested by applying heat with uncontrollable heat sources i e heat guns torches etc as this can permanently damage the thermostat or other parts of the damp...

Page 12: ...ves the right to change specifications without notice Product warranties can be found online at Greenheck com either on the specific product page or in the literature section of the website at Greenheck com Resources Library Literature Phone 715 359 6171 Fax 715 355 2399 Parts 800 355 5354 E mail gfcinfo greenheck com Website www greenheck com Our Commitment ...

Reviews: